4.5 Storage and transport
To store or decommission a UPS-option power supply for a longer period of time the batteries inside should be fully charged, for that
connect the power supply for at least 8h to mains. Store in upright position inside a dry and frost-free room.
WARNING!
WARNING!
It is not allowed to transport the crate with the battery fuse installed. Make sure the fuse is removed to guarantee a
safe handling of the product.
CAUTION!
CAUTION!
If the crate is not in use for more than 6 months, it needs to be connected to mains for at least 8 hours to make sure,
the batteries are charged to full capacity again.
INFORMATION
INFORMATION
There are no restrictions for rail, road, sea and air transportation (IATA, DGR clause A67).