background image

Technical documentation

Last changed on: 07.10.2019

ECH 54A / 55A / 56A

10 Slot 19” Crate for MMS – Low and High Voltage Power Supply Modules

Up to 10 MMS-HV or MMS-LV Power Supply Modules

Up to 3,000 W power

wide range of HV- and LV-modules

compatible to CC24 / CC23 Controller boards with integrated iCS Linux Server or Wiener 
Mpod Controller

optional UPS

robust mechanics, module front and back reversible

www.iseg-hv.com

Summary of Contents for ECH 54A

Page 1: ...Voltage Power Supply Modules Up to 10 MMS HV or MMS LV Power Supply Modules Up to 3 000 W power wide range of HV and LV modules compatible to CC24 CC23 Controller boards with integrated iCS Linux Server or Wiener Mpod Controller optional UPS robust mechanics module front and back reversible www iseg hv com ...

Page 2: ...r use of the device Important security information It is strongly recommended to read the operator s manual before operation To avoid injury of users it is not allowed to open the unit There are no parts which can be maintained by users inside of the unit Opening the unit will void the warranty We decline all responsibility for damages and injuries caused by an improper use of the module It is str...

Page 3: ...power supply 7 4 2 Forced air cooling 8 4 3 Replacing the fan tray or airfilter mat 9 4 4 UPS maintenance and security advice 10 4 5 Storage and transport 11 4 6 Replacing the battery fuse 12 5 Compatibility lists 12 6 Dimensional drawing 13 7 Accesories 15 8 Appendix 15 9 Warranty service 16 10 Disposal 16 11 Manufacturer s contact 16 ECH5xA 10 Slot MMS Crate Last modified on 07 10 2019 www iseg ...

Page 4: ...unication of the MMS modules a crate controller needs to be plugged into a special Crate Controller Slot The ECH 5xA is compatible with iseg CC24 Master CC23 Slave Controller and Wiener MPOD controller The CC24 Master controller is equipped with integrated Linux server hardware running iseg iCS System ethernet and optional WiFi connectivity Up to eight CC23 Slave controller can extend a CC24 syste...

Page 5: ...eration temperature 0 50 C ambient without derating Storage temperature 30 C 85 C 55 C with UPS option Stability 10 mV or 0 1 24 hours 25 mV or 0 3 6 month under constant conditions Floating DC Power Supply 50V 50V M F O T Maintenance Free Operation Time Internal fans 40 C ambient 65 000 h 25 C ambient 100 000 h electronics 40 C ambient 100 000 h Dimensions L W H 463mm 19 8U Weight 31 5kg 10 kg wi...

Page 6: ...mended to cover unused module slots with blind front panels Z514569 CAUTION CAUTION For UPS option only Before operating the first time please make sure the battery fuse is inserted into the power supply Before operation and connecting to mains please make sure that all cables are connected and airflow is not impeded The case must not be covered and installed properly The crate controller and modu...

Page 7: ...th setting the crate into standby mode disconnect it from mains and wait a few minutes Now remove the blue sticker at the bottom of the back cover arrow at Figure 1 and proceed with unscrewing the four Phillips screws and carefully detach the lid beginning from the top side Before completely removing the back cover it is necessary to disconnect the ribbon cable of the attached switch circuitboard ...

Page 8: ... is needed to completely remove the power supply from its support frame Figure 3 remove wire tie and loosen screws Now replace the power supply and reassemble in reverse order tie down the internal mains cable on the handle 4 2 Forced air cooling The crate offers an internal forced air cooling with temperature dependent speed regulation by the crate controller The fresh air intake is on the bottom...

Page 9: ...gure 6 pull out tray After removing the case lid use the Allen head screw driver to unscrew the two tray retainers and pull out the fan tray assambly Reassemble in reverse order UPS uninterruptible power supply optional The ECH 5XA can be optionally equipped with a battery driven uninterruptible power supply UPS for the HV module power rail Its purpose is to provide emergency power to the HV modul...

Page 10: ...orking condition a contact with the electrolyte is impossible If the batteries get damaged do not touch any exposed electrolyte WARNING WARNING When changing the UPS option power supply The batteries inside are heavy handle with care as they are sensitive to mechanical damage CAUTION CAUTION Do not dispose a UPS option power supply in the normal household wastes as the contained batteries have to ...

Page 11: ...ed to transport the crate with the battery fuse installed Make sure the fuse is removed to guarantee a safe handling of the product CAUTION CAUTION If the crate is not in use for more than 6 months it needs to be connected to mains for at least 8 hours to make sure the batteries are charged to full capacity again INFORMATION INFORMATION There are no restrictions for rail road sea and air transport...

Page 12: ...use Fuse specification Automotive blade fuse size MAXI rated 32VDC 50A time delay 5 Compatibility lists MMS CRATE CONTROLLERS NOTES CC24 Master controller with Linux and iCS2 Ethernet and WiFi 2 Slave CAN Lines All series CC23 Slave controller Slave controller for use with CC24 system All series Wiener MPOD Controller MPOD Controller built since 2016 MMS HIGH VOLTAGE MODULES NOTES EHS series Stand...

Page 13: ...6 Dimensional drawing Figure 8 ECH 5xA ECH5xA 10 Slot MMS Crate Last modified on 07 10 2019 www iseg hv com 13 16 ...

Page 14: ...Figure 9 ECH 5xAHVR ECH5xA 10 Slot MMS Crate Last modified on 07 10 2019 www iseg hv com 14 16 ...

Page 15: ...ANbus Adapter RJ45 to SUB D 9 female Z583401 Genuine power cable EU Plug Z201447 Front panel blind RAL9001 6U 8HP Z514569 Spare fan tray Z520167 Spare power supply 1200W Z520170 Spare uninterruptible power supply 1200W Z520168 Front panels Z514569 8 Appendix For more information please use the following download links This document http download iseg hv com SYSTEMS MMS ECH iseg_manual_ECH5xA_en pd...

Page 16: ...com en support rma 10 Disposal INFORMATION All high voltage equipment and integrated components are largely made of recyclable materials Do not dispose the device with regular residual waste Please use the recycling and disposal facilities for electrical and electronic equipment available in your country 11 Manufacturer s contact iseg Spezialelektronik GmbH Bautzner Landstr 23 01454 Radeberg OT Ro...