ise smart connect Modbus Vaillant 

Product Manual

 

 

Product Manual 

ise smart connect Modbus Vaillant

 

Order no. S-0002-007 
Complete set for installation, consisting of the two system components: 
- ise smart connect Modbus Vaillant and 
- ise eBUS Adapter 
 
Order no. 1-0009-000 
- ise smart connect Modbus Vaillant 
 
Order no. 2-0001-003 
- ise eBUS Adapter 
 
Valid for firmware version 1.0 
 
 

 

    

 

 

Summary of Contents for 1-0009-000

Page 1: ...Modbus Vaillant Order no S 0002 007 Complete set for installation consisting of the two system components ise smart connect Modbus Vaillant and ise eBUS Adapter Order no 1 0009 000 ise smart connect M...

Page 2: ...TCP IP 16 4 1 Modbus function codes 16 4 2 Modbus exception codes 16 4 3 Modbus TCP IP Gateway behaviour 16 4 4 Modbus TCP IP unit IDs 17 4 5 Modbus Registers 17 4 5 1 Unit ID 1 Vaillant geoTHERM 3 1...

Page 3: ...ge of the ise smart connect Modbus Vaillant 33 8 3 The ise smart connect Modbus Vaillant does not work 34 9 License agreement ise smart connect Modbus Vaillant software 35 9 1 Definitions 35 9 2 Objec...

Page 4: ...ise smart connect Modbus Vaillant Product Manual Order No S 0002 007 Product Manual Page 4 45 11 GNU GENERAL PUBLIC LICENSE 41...

Page 5: ...e ise eBUS Adapter is a system component to connect the Vaillant bus modular control with the Modbus system It connects devices of the ise smart connect series for eBUS connection in this case ise sma...

Page 6: ...art connect Modbus Vaillant Product description Order No S 0002 007 Product Manual Page 6 45 1 3 Function schematic eBUS Modbus TCP IP Building Management System BMS Accessory geoTHERM 3 VWS220 3 460...

Page 7: ...LED APP green Green Normal operation Off Flashing For diagnosis code see 5 2 1 5 2 2 5 LED COM yellow Yellow Normal operation Modbus TCP IP server running brief dark phases indicate Modbus TCP IP tele...

Page 8: ...il as per DIN EN 60715 vertical mounting network connections must face downward Observe temperature range 0 C to 45 C do not install over heat emitting devices and ensure sufficient ventilation coolin...

Page 9: ...n the connection area The cap is mounted with an attached power supply terminal and a connected power supply line to the rear Mounting the cover cap The cover cap is pushed over the supply terminal un...

Page 10: ...versal 2 LED PWR green Green Minimum voltage from eBUS is connected 3 LED COM green Green Connection of ise smart connect Modbus Vaillant with eBUS established 4 USB connection Important note The adap...

Page 11: ...executing the building management system BMS will establish the connection to the ise eBUS Adapter Figure 4 Junction box for the connection of the ise eBUS Adapter to the heating system The position o...

Page 12: ...lso supplying a KNX line Chapter 2 3 3 Connect the ise eBUS Adapter with the eBUS in the intended junction box Important note The maximum length of the eBUS connection cable is 125 m Chapter 2 5 4 Ins...

Page 13: ...soon as a DHCP server will be available a new IP address will be automatically assigned to the de vice If it is necessary to use static IP setup go to the IP network settings page of the device websi...

Page 14: ...protocol of the executing company for heating air conditioning ventilation technology to the building technology planner to check which units are available in the installation and need to be enabled...

Page 15: ...ge the Modbus TCP IP port of the device on the website You can find this op tion on the Vaillant components subpage By default the port is 502 It is possible to configure a port in the range between 2...

Page 16: ...rted dependant on the request 04 0x04 Server Failure The server failed during the execution 11 0x0B Gateway Target Device Failed To Respond Indicates that no response was obtained from the target devi...

Page 17: ...Modbus Registers 4 5 1 Unit ID 1 Vaillant geoTHERM 3 4 5 1 1 Input Registers R Addr Name Datatype Polling interval min Range Reso lution Unit 1 eBUS error eBusErrorState 2 eBUS last error eBusError 3...

Page 18: ...2 DTC_EHP 15 32 Error history 3 DTC_EHP 15 33 Error history 4 DTC_EHP 15 34 Error history 5 DTC_EHP 15 35 Error history 6 DTC_EHP 15 36 Error history 7 DTC_EHP 15 37 Error history 8 DTC_EHP 15 38 Erro...

Page 19: ...63 Set back temperature uint16_t 2 5 50 C 64 65 Heating curve IEEE 754 single float 2 0 1 4 0 0 05 66 Maximum target flow temperature uint16_t 2 15 80 C 67 Minimum target flow temperature uint16_t 2...

Page 20: ...ange Reso lution Unit 6 Backup hysteresis uint16_t 2 1 20 K 7 Energy integral since backup heater started int16_t 2 740 50 min 8 Bivalent temperature int16_t 2 9 10 C 9 Backup heater mode for CH backu...

Page 21: ...off threshold uint16_t 2 5 50 C 4 5 5 Unit ID 12 14 18 Vaillant VR90 heating circuit 2 4 8 4 5 5 1 Input Registers R Addr Name Datatype Polling interval min Range Reso lution Unit 1 eBUS error eBusEr...

Page 22: ...or heat source outlet sensor 528 51 Error condenser sensor 529 60 Error Heat source anti freezing protection Delta T6 T7 530 61 Error Heat source anti freezing protection T5 4 C 531 62 Error Heat sour...

Page 23: ...65 High pressure cut off during cooling operation 566 4WV did not switch 567 CH circuit freezing protection during cooling operation 568 Low pressure during cooling operation 569 Refrigerant temperatu...

Page 24: ...Acceleration mode 13 Frost protection Heating 14 Frost protection Cylinder 15 Legionella protect 16 Automatic pump spin 17 Floor drying 18 Venting mode 19 Fault shutdown Heating 20 Error shutdown Hea...

Page 25: ...mart connect Modbus Vaillant Modbus TCP IP Order No S 0002 007 Product Manual Page 25 45 4 6 9 opModeDHW Value Description 1 On 2 Off 3 Auto 4 6 10 opModeHC Value Description 1 On 2 Off 3 Auto 4 Eco 5...

Page 26: ...al operation Off Flashing For diagnosis code see 5 2 1 5 2 2 5 LED COM yellow Yellow Normal operation Modbus TCP IP server running brief dark phases indicate Modbus TCP IP telegram traffic Off Flashin...

Page 27: ...is switched on or after a re turn in voltage occurs the device indicates its status through the following LED combinations LED APP green LED COM yellow Meaning Off Off No power supply Please check con...

Page 28: ...supply Three slow flashes fol lowed by a 2 s pause eBUS Error Error in communication with the ise eBUS Adapter Communication be tween the ise smart connect Modbus Vaillant and the ise eBUS Adapter is...

Page 29: ...hed off Press and hold button 1 and switch on the device Press and hold button 1 until the LED 3 the APP LED 4 and the COM LED 5 flash slowly simultaneously Briefly release the button 1 then press and...

Page 30: ...in the message The update can be started with the button Perform update In case of an incompatibility the start of the update has to be confirmed once more 5 5 2 Local Update without Internet Access...

Page 31: ...ed USB cable as standard Please note that the use of USB cables with a length of more than 3 m is gener ally not permitted Supported protocols ARP ICMP IGMP UDP IP DHCP AutoIP Modbus TCP IP as per Mod...

Page 32: ...8 2 Device status page of the ise smart connect Modbus Vail lant Are there software updates for my ise smart connect Modbus Vaillant device Please read about this in chapter 5 5 Firmware Update Pleas...

Page 33: ...of the device To do so proceed as follows Call up the website of the device see chapter 5 3 Accessing the website of the device Select Download Log File in the upper menu bar on the status page The pa...

Page 34: ...IP settings you need to do a factory reset in accordance with chapter 5 4 1 and attach the device to a network provid ing DHCP service O K N O If neither the approaches above nor chapter 7 provide a s...

Page 35: ...ant software The Licensor grants the Licensee the non exclusive non transferable right to use the ise smart connect Modbus Vaillant software for an unlimited time in accordance with the following cond...

Page 36: ...ntiality 9 5 1 Documentation The ise smart connect Modbus Vaillant software and the documentation which shall be provided in printed form or also as online help or online documentation are business se...

Page 37: ...f the use of the ise smart connect Modbus Vaillant software even if the Licensor is aware of the possibility of damage of that type This limitation of liability is valid for all damage claims of the L...

Page 38: ...llant software Order No S 0002 007 Product Manual Page 38 45 9 11 Subsidiary agreements and changes to the agreement Subsidiary agreements and changes to the agreement shall only be valid in writing 9...

Page 39: ...ce Copyright 1992 2013 by Linus Torvalds et al Software package Buildroot Version of the software 2012 11 Source http buildroot org License GNU GPL Version 2 June 1991 Copyright notice Copyright 1999...

Page 40: ...libzip Version of the software 1 1 2 Source https nih at libzip License https nih at libzip LICENSE html Copyright notice Copyright c 1999 2016 Dieter Baron and Thomas Klausner The license texts of th...

Page 41: ...it in new free programs and that you know you can do these things To protect your rights we need to make restrictions that forbid anyone to deny you these rights or to ask you to surrender the rights...

Page 42: ...an appropriate copyright notice and disclaimer of warranty keep intact all the notices that refer to this License and to the absence of any warranty and give any other recipients of the Program a copy...

Page 43: ...der the terms of Sections 1 and 2 above on a medium customarily used for software interchange or b Accompany it with a written offer valid for at least three years to give any third party for a charge...

Page 44: ...whether by court order agreement or otherwise that contradict the conditions of this License they do not excuse you from the conditions of this License If you cannot distribute so as to satisfy simult...

Page 45: ...o the Free Software Foundation we sometimes make exceptions for this Our decision will be guided by the two goals of preserving the free status of all derivatives of our free software and of promoting...