Use the holes in the brackets to secure the switch to a wall or panel.
3.3
Chassis Ground Connection
The iES20G chassis ground connection uses a #6-32 Screw. We recommend terminating the ground
connection using a #6 ring lug, and a torque setting of 15 in.lbs (1.7Nm). The red outline indicates the
location of the chassis ground.
3.4
Power Connections
The iES20G Series Ethernet switch supports 3 different dual redundant power supplies (PWR1 and PWR2):
1.
LV: Dual Input 10-48VDC
2.
MV: Dual Input 36-75VDC
3.
HV: Single Input 85-264VAC or 88-370VDC with a Single 10-48VDC Backup.