background image

 

MANUAL

 • Subject to alteration! Version: 07.01.2022 

 

ipf electronic gmbh

 

 

Rosmarter Allee 14

 • 

58762 Altena 

• Germany 

 Tel +49 2351 9365-0 • [email protected] 

 

www.ipf-electronic.com

   

 

1

 

 

IN32E332-S 

Inductive proximity switsch 

IV56E205-S 

Amplifier 

VKC0E333-S

 

Cable socket 

 
Installation of the sensor 

 

The sensor 

IN32E332-S

 

is an inductive proximity switch for non-flush mounting. Due to its construction, 

the device only detects metallic objects.

 

 

To achieve the nominal switching distance of 15mm (see technical data), must have the metal part 

following properties: 

Material: 

ST37 

Dimensions:  32mm x 32mm x 1mm 

For other materials, the correction factors are listed in the technical data.

 

 

The switching distance may deviate from the nominal value by ±20% due to component tolerances. 

 

Install the device in a way, that the plastic cap is not surrounded by metal. The lateral distance to metallic 

objects must be at least 32mm.  

 

To avoid damaging the threaded sleeve during assembly, the tightening torque must not exceed 150 Nm.  

 

The device may be used in surroundings with temperatures up to 230°C.  

 
 

Installation of the amplifier 

 

The amplifier 

IV56E205-S

 is to be used for the operation of the sensor IN32E332-S in connection with the 

cable socket VKC0E333-S. 

 

The device is suitable for mounting on a DIN rail. Mounting must take place outside the dust-ex-area, e.g. 

in a protected switch cabinet. 

 

The pnp switching output can be further processed with a PLC. The switching output has a switch-on delay 

of 100ms. 

 

Elektrical connection 

Connection of the sensor to the amplifier via the 

VKC0E333-S cable socket: 
 
 
Connection of the operating voltage and the switching 

output to the amplifier. 
 
 
 

IMPORTANT: 

 

Switch off the operating voltage before connecting or disconnecting the amplifier! 

 

The cable socket may also only be plugged in or unplugged from the sensor when it is de-energized. An 

appropriate waiting time (>10s) must be observed before pulling off.  

 

When plugging in the cable socket, make sure that, that it snaps securely into the connector of the sensor. 

 

Clamp 4: 

brown (sensor power 3V) 

Clamp 5: 

black (screen) 

Clamp 6: 

blue (sensor power supply GND) 

 

Clamp 9: 

+ U

B

 

Clamp 8: 

switching output pnp, no, 400mA  

Clamp 7: 

0V (GND) 

 