background image

IPEX System 636

® 

Concentric Vent Termination Kits.

Installation Instructions for 2", 3" and 4"

These instructions are to be followed in conjunction with those
found in the IPEX System 636 Installation Guide. The installation
guide is available in every box of System 636 45° Elbows or
on the web at 

www.ipexinc.com

.

System 636 Pipe, Fittings, Termination Kits and Cements are
certified as a system and must be installed as such. Different
manufacturers have different materials, joining systems and
adhesives. Do NOT mix pipe, fittings, cements, or joining
methods from different BH Vent manufacturers, this can result in
unsafe conditions and will 

void the certification

System 636 PVC/CPVC concentric vent kits are made from
certified compounds. PVC kits are rated to 65ºC maximum and
CPVC kits are rated to 90ºC maximum. 

All termination kits must be located and installed in accordance
with local building code and 

CSA B149.1 Natural Gas and

Propane Installation Code

.

Concentric Vent Kit Assembly

1. Once the proper location has been determined, cut a hole

in the roof or wall large enough to accommodate the outer
pipe. The size of the hole can vary greatly depending on
the roof pitch.

2. As per the procedures outlined in the 

System 636

Installation Guide

, solvent cement the inner pipe to the

concentric Wye fitting.

3. Solvent cement the outer pipe to the concentric Wye fitting. 

4. Slide the assembly through the roof or wall penetration.

(Install flashing if needed)

5. To permanently affix the rain cap, it should be solvent

cemented to the inner pipe. For installations where removal
of the cap may be required for service or cleaning the cap, it
can be fastened mechanically (see instructions below). For
either installation method, the outer pipe is only a friction fit
with the cap.

6. Once the rain cap is installed, and the kit secured as outlined

below, the kit can be connected to the venting system.

A

B

D

D

C

E

G

1

2

3

4

5

45º

F

System 636 Concentric Vent Kits

Termination Kits Include:

Dimension (Inches)

A

B*

C

Nominal Pipe Size

F

G

Item #

Concentric Kit

D

E

196005

2" x 16"        PVC

29.0

16.5

3.5

2

2

7.38

1.75

196006

3" x 20"        PVC

36.1

20

4.5

3

3

8.75

2.25

196105

2" x 28"        PVC

41.0

28

3.5

2

2

7.38

1.75

196125

2" x 40"        PVC

53.0

40

3.5

2

2

7.38

1.75

196106

3" x 32"        PVC

48.1

32

4.5

3

3

8.75

2.25

196116

3" x 44"        PVC

60.1

44

4.5

3

3

8.75

2.25

196021

4" x 36"        PVC

56.0

37.3

6.62

4

4

10.00

3.50

197009

3" x 20"        CPVC

36.1

20

4.5

3

3

8.75

2.25

197107

3" x 32"        CPVC

48.1

32

4.5

3

3

8.75

2.25

197117

3" x 44"        CPVC

60.1

44

4.5

3

3

8.75

2.25

197021

4" x 36"        CPVC

56.0

37.3

6.62

4

4

10.00

3.50

1 Wye - (Concentric)

B* Dimension be may be shortened to a minimum of 12". Inner pipe (item 3)
must remain "F" inches longer than the outer pipe (item 4). Cut pipe ends
square and solvent cement as outlined in the System 636 installation manual.
C

Installation cutout should be at least 1/2" larger than dimension “C”.

Lengthening the units is not permitted.

2 Rain Cap
3 Exhaust Vent Pipe (Inner)
4 Fresh Air Intake Pipe (Outer)
5 Stainless Steel Screw & Nut

Canadian Customers

US Customers

Toll Free: (866) 473-9462          

www.ipexinc.com

Toll Free: (800) 463-9572          

www.ipexamerica.com

Air Intake

Distance above avg.
snow fall or grade
Ref: CSA B149.1

Exterior wall

1” Min
2” Max
(From wall
or Face Plate)

Clamp or Strap
(Field Supplied)

Exhaust

Air Intake

Exhaust

Air Intake

Distance above avg.
snow fall or grade
Ref: CSA B149.1

Flashing

(Field Supplied)

Roof

Clamp or Strap
(Field Supplied)

Exhaust

Air Intake

Exhaust

Roof Termination

4”

MAX

4”

MAX

24” MIN

24” MIN
to next CVK

Sidewall Termination for Multiple Horizontal

Concentric Vent

Wall Termination

Figure C: Typical CVK Spacing

Figure B

Figure A

Installation / Support Procedures

1. Kits must be securely fastened to structure, to ensure dimensions

shown below are maintained.

2. Straps are field supplied. Use straps, clamps or equivalent that

will not score or damage the pipe. Expansion and contraction
should be addressed between appliance and termination point.

3. All penetrations must be sealed according to local building

codes. Caulking for side wall terminations and flashing for roof
penetrations are typical. Use only PVC/CPVC compatible sealing
material, contact IPEX for a complete list.

4. The weight of the concentric kits must be supported by the

clamps/straps and not by the vent system it connects to.

5. Insulating exhaust piping in unconditioned space to prevent

freezing may be required by code. 

6. For multiple horizontal installations, keep Concentric Vent Kit

gaps close (up to 4" apart) or over 24" apart.

These guidelines are not appliance specific; OEM manufacturers
may supply spacing guidelines particular to each appliance. In
this case the manufacturer’s recommendations shall supersede
those described herein. 

To prevent flue gas from recirculating, IPEX recommends installing
multiple concentric kits as follows:  

2 concentric vent kits: either maintain a 24” minimum distance
apart, or have the rain caps no more than 4” apart  

3 concentric vent kits: Option 1 - keep all 3 kits at least 24”
apart. Option 2 - group 2 kits close up to a maximum of 4” apart
and the third kit over 24” apart. 

4 or more concentric vent kits: Option 1 - keep all concentric kits
at least 24” apart. Option 2 – group the CVK’s in pairs, having 2
kits close together to a maximum of 4” apart, keeping the next
grouping of 2 kits over 24” away. As per Figure C.

The dimensions shown in Fig. C, are distances between the edges
of the rain caps. 

7. The pipe length of the concentric vent kit can be shortened;

providing that the cutting and cementing procedures adhere to
the System 636 guidelines.

8. Pipe lengths and/or fittings can added to the socket of the rain

cap in order to divert the exhaust gas; providing that the
appliance manufacture confirms that the extra length or changing
in direction will not adversely impact the flow of flue gas

Mechanically Fastened Rain Cap

The Rain Cap must be installed with the supplied Stainless Steel
screwand lock nut, and in accordance with the instructions and
diagram below.

1. Locate the drill location dimple on the outside of the rain cap.

2. At this location, drill through the cap and the inner pipe wall.

Ensure that the path of the hole is perpendicular to the inner pipe
NOT the outside of the cap. For the 2" & 3" kit, drill a 3/16"
hole, for the 4" kit, a 1/4" hole.

3. Insert the screw and tighten the bolt, do not over tighten. 

Reviews: