IMPORTANT SAFEGUARDS

When using electrical equipment, basic safety precautions should always be followed, including the following:

READ AND FOLLOW ALL SAFETY INSTRUCTIONS

1.

CAUTION – To prevent electrical shock, do not mate unit connector until installation is complete and A.C.
power is supplied to the unit.

2.

CAUTION – This fixture provides more than one power supply output source. To reduce the risk of electrical

shock, disconnect both normal and emergency sources by turning off the A.C. branch circuit and by discon-
necting the unit connector.

3.

CAUTION – This is a sealed unit. Components are not replaceable. Replace the entire unit when necessary.

4.

CAUTION – Installation and servicing should be performed by qualified personnel only. De-energize before
opening.

5.

The 

ILB is for use with grounded LED luminaires listed to UL standards.  Not for use in heated air outlets or

hazerdous locations.

6.

The 

ILB requires an unswitched A.C. power source of 120 to 277 volts, 50/60 Hz.

7.

The 

ILB and A.C. driver must be on the same branch circuit.

8.

Do not mount near gas or electric heaters.

9.

The 

ILB should be mounted in locations and at heights where it will not readily be subjected to tampering by

unauthorized personnel.

 10. The 

ILB will supply 10-60 VDC output at the individual rated specification for 90 minutes. See individual units

for output specifications.

11. Suitable for use in damp locations and plenum spaces.
12. Suitable for Luminaires, recessed Type IC (intended for insulation contact).
 13. For use in 0° C minimum, 55° C maximum ambient temperatures.
 14.  The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition, void

warranty, and result in non-compliance with UL specifications.

 15. Do not use this equipment for other than intended use.

 16. Install in accordance with the National Electrical Code and local regulations.

17. Lighting fixture manufacturers, electricians, and end-users need to ensure product system compatibility before

final installation. See addendum for compatibility and covered luminaire requirements.

INSTRUCTION MANUAL

SAVE THESE  INSTRUCTIONS

ILB-CP

‘A’ MOUNTING DESIGN

 

EMERGENCY LIGHTING EQUIPMENT

 

FOR LED

Patented

EMERGENCY LED DRIVER FOR USE 
WITH LED LUMINAIRES IDENTIFIED IN 
THE MANUFACTURER’S INSTALLATION 
INSTRUCTIONS
E473237

CLASS 2 OUTPUT

Summary of Contents for ILB-CP Series

Page 1: ...ear gas or electric heaters 9 The ILB should be mounted in locations and at heights where it will not readily be subjected to tampering by unauthorized personnel 10 The ILB will supply 10 60 VDC output at the individual rated specification for 90 minutes See individual units for output specifications 11 Suitable for use in damp locations and plenum spaces 12 Suitable for Luminaires recessed Type I...

Page 2: ...iling The flex conduit marked A should be wired into the driver lamp compartment or to an electrical junction box on the fixture which allows access to the fixture connections Refer to Illustration 1 for typical mounting When battery packs are remote mounted consult Customer Service for the maximum allowable distance between the battery pack and the load Illustration 1 Downlight Fixture FLEX A JUN...

Page 3: ... as intended The ILB is in the standby charging mode The TBTS will be lit providing a visual indication that the battery is being charged Emergency Mode The A C power fails The ILB senses the A C power failure and automatically switches to the Emergency Mode One or multiple LEDs are illuminated for a minimum of 90 minutes When the A C power is restored the ILB switches the system back to the Norma...

Page 4: ...rge before conducting a one hour test The ILB is a maintenance free unit however periodic inspection and testing is required NFPA 101 Life Safety Code outlines the following schedule Monthly Insure that the TBTS light is illuminated Conduct a 30 second discharge test by depressing the TBTS At least one LED should operate at reduced output Annually Insure that the TBTS is illuminated Conduct a full...

Page 5: ...aire manufacturer name and part number Click on Search tab to open the Qualified Products List Determine per RATED DATA efficacy shown in lumens per watt lm w Multiply lumens per watt by ILB CP rated output example lm w x 5 watts Refer to table ILB MODEL SPECIFICATION CHART below for the wattage of the specific ILB CP model to be used in the luminaire lm w x ILB CP Watts Minimum emergency lumens o...