IPE300 series engineering VFD
Extension card
-304-
A.3 Wiring
Ground a shielded cable as follows:
Grounding position of the
shielded cable
Grounding position of
the shielded cable
Figure A-4 Extension card grounding diagram
A.4 I/O extension card 1 (EC-IO501-00)
The terminals are arranged as follows:
CME and COM are shorted through J3 before delivery, and J5 is the jumper for selecting the output
type (voltage or current) of AO2.
AI3
AO2
GND
COM
CME
Y2
S5
RO3A
RO3B
RO3C
PW
+24V
S6
S7
S8
RO4A
RO4C
Indicator definition:
Indicator
Definition
Function
LED1
Status indicator
This indicator is on when the extension card is
establishing a connection with the control board;
it blinks periodically after the extension card is properly
connected to the control board (the period is 1s, on for
0.5s, and off for the other 0.5s);
and it is off when the extension card is disconnected from
the control board.