IPE300 series engineering VFD
Function parameter list
-229-
Function
code
Name
Description
Default Modify
P90.14
Bit 14 selection
of CW 1
20: Remote brake output (0: diable; 1: Brake
output relay is valid, corresponding to output
terminal 50: remote brake)
21: Reserved
22: Clear encoder pulse count (0: disable; 1: Set
the present encoder pulse count to the value of
P22.24.)
23
–32: Reserved
0
◎
P90.15
Bit 15 selection
of CW 1
0
◎
P90.16
Partial function
selection 1 of
CW 1
0x0000
–0x2111
Ones place: OFF1 power-off and restart
0: OFF1 rising edge + RUN high level startup
1: OFF1 rising edge + RUN rising edge startup
Tens place: OFF2 communication control enable
0: Select the bit of OFF2 as 1 for the forced
control word 1, i.e. not activated
1: Select the bit value of OFF2 for the received
control word 1
Note:
When the terminal/keypad gives a free
stop command, this bit is invalid.
Hundreds place: OFF3 communication control
enable
0: Select the forced control word 1 to the bit of
OFF3 as 1, i.e. not activated
1: Select the bit value of OFF3 for the received
control word 1
Thousands place: Switch to local
0: “18: Run command to switch between local
a
nd remote” in CW 1 is not identified.
1: Identify “18: Run command to switch between
local and remote” in CW 1, and switch to the local
keypad.
2: Identify “18: Run command to switch between
local and remote” in CW 1, and switch to the local
terminal.
0x0000
◎
P90.17
Partial function
selection 2 of
CW 1
0x0000
–0x1111
Ones place: Enabling ramps setting of CW1
0: Disable
1: The value of the "ramp setpoint" bit selected in
control word 1 is valid.
0x0000
◎