Goodrive350-19 series VFD for crane
Commissioning guidelines
-52-
5.4.6 Controlling the vortex module through the AO terminal
Braking resistor
PB
(+)
R
S
T
U
V
W
VFD
R
S
T
AO
COM
Vortex module
M
3~
M
3~
I
V
Figure 5-6 Connecting the AO terminal to the vortex module
Note: Turn SW2 on the control board to "V" for voltage output.
Controlling the vortex module through the AO terminal
1. Connect the AO terminal to the vortex module according to the figure.
2. Set P06.14=0 to select running frequency output for AO1.
3. Set P06.17
–P06.21 to adjust the vortex module output voltage percentage.
The output voltage percentage is the ratio of running frequency to P00.03.
Function code settings:
Function
code
Name
Description
Default
P06.14
AO1 output
0: Running frequency
0
P06.17
AO1 output lower limit
-300.0%
–P06.19
16.0%
P06.18
AO1 output corresponding to
lower limit
0.00V
–10.00V
2.00V
P06.19
AO1 output upper limit
P06.17
–100.0%
60.0%
P06.20
AO1 output corresponding to
upper limit
0.00V
–10.00V
10.00V
P06.21
AO1 output filter time
0.000s
–10.000s
0.000s