Goodrive350-19 series VFD for crane
Commissioning guidelines
-40-
6. Perform low-speed trial run.
5.1.3 Macro parameters (P90.00=1)
Function
code
Name
Setting
Remarks
P00.00
Speed control mode
1
Sensorless vector control (SVC) mode
1
P00.01
Channel of running
commands
1
Terminal
P00.03
Max. output frequency
100.00Hz
P00.04
Upper limit of running
frequency
100.00Hz
P00.06
Setting channel of A
frequency command
6
Multi-step speed run
P00.11
ACC time 1
6.0s
P00.12
DEC time 1
4.0s
P01.01
Starting frequency of
direct start
1.00Hz
P01.15
Stop speed
1.50 Hz
P05.03
Function of S3
85
Enable brake detection
P05.04
Function of S4
7
Fault reset
P06.03
RO1 output
49
Brake output
P10.04
Multi-step speed 1
8.0%
P10.06
Multi-step speed 2
33.0%
P10.08
Multi-step speed 3
50.0%
P10.10
Multi-step speed 4
70.0%
P10.12
Multi-step speed 5
100.0%
P11.08
VFD/motor OL/UL
pre-alarm selection
0x021
Enable underload protection to
enhance equipment safety.
P11.11
Underload pre-alarm
detection threshold
15%
P25.01
Function of S5
75
Brake feedback signal
P25.02
Function of S6
16
Multi-step speed 1
P25.03
Function of S7
17
Multi-step speed 2
P25.04
Function of S8
18
Multi-step speed 3
P90.04
Enabling brake-oriented
logic
1
The brake is controlled by the VFD.
P90.14
Forward brake release
torque
40.0%
Corresponding to the motor rated
torque