Goodrive350-19 series VFD for crane
Installation guidelines
-37-
Terminal
Description
PT1+
Independent PT100 and PT1000 inputs: PT1+ connects to PT100 resistor, while
PT2+ connects to PT1000 resistor.
•
Resolution: 1°C
•
Range: -20°C
–150°C
•
Detection precision: 3°C
•
Supporting offline protection
PT2+
PT-
Reference zero potential of PT100/PT1000
RO3A
RO3 outputs. RO3A: NO; RO3C: common
Contact capacity: 3A/AC250V, 1A/DC30V
RO3C
RO4A
RO4 outputs. RO4A: NO; RO4C: common
Contact capacity: 3A/AC250V, 1A/DC30V
RO4C
PW
Used to provide input digital working power from the external to the internal
Voltage range: 24(-20%)
–48VDC(+10%), 24(-10%)–48VAC(+10%) voltage input
+24V
User power supply provided by the VFD. Max. output current: 200mA
COM
+24V common terminal
S5
Digital input 5
• Internal impedance: 6.6kΩ
• Supporting the voltage input of external power
(-20%)24
–48VDC(+10%) and (-10%)24–48VAC(+10%)
• Supporting the internal power 24V
• Bi-direction input terminal, supporting both NPN and PNP
• Max. input frequency: 1kHz
• All are programmable digital input terminals, the functions of
which can be set through function codes
S6
Digital input 6
S7
Digital input 7
S8
Digital input 8
It supports PTC input, while PTC acts at 2.5kΩ, and it supports the
input of only dry contacts sharing COM.
Note:
You can install optional expansion cards for 1.5
–5.5kW VFD models and you are recommended
to install them at slot 2.
I/O expansion card 2 has been installed at slot 3 for 7.5kW and higher VFD models as standard
configuration.
4.5 Wiring protection
4.5.1 Protecting the VFD and input power cable in case of short circuit
The VFD and input power cable can be protected in case of short circuit, avoiding thermal overload.
Carry out protective measures according to the following figure.