Goodrive20-EU Series VFD
Function parameters
-95-
Function
code
Name
Description
Default Modify
1: STO alarm unlocked
STO alarm unlocked means when STO appears,
STO alarm will disappeared automatically after
state recovery.
Note:
STL1
–STL3 are fault lock and cannot be
reset.
P13 group SM control
Function
code
Name
Description
Default Modify
P13.09
Frequency
switching
point
0.00
–630.00
50.00
○
P13.13
Short circuit
brake current
After the VFD starts, when P01.00=0, set P13.14
to non-zero value and begin short circuit braking.
After the VFD stops, when the operation
frequency is less than P01.09, set P13.15 to
non-zero value and begin stopping short-circuit
braking and then DC braking.
Setting range of P13.13: 0.0
–150.0% (relative to
the percentage of rated current of the VFDs)
Setting range of P13.14: 0.00
–50.00s
0.0%
○
P13.14
Hold time of
short circuit
brake at start
0.00s
○
P13.15
Hold time of
short circuit
brake at stop
0.00s
○
P14 group Serial communication
Function
code
Name
Description
Default Modify
P14.00
local
communication
address
Setting range: 1
–247
When the master is writing the frame, the
communication address of the slave is set to 0;
the broadcast address is the communication
address. All slaves on the Modbus fieldbus can
receive the frame, but the salve doesn't answer.
The communication address of the drive is
unique in the communication net. This is the
fundamental for the point to point communication
between the upper monitor and the drive.
Note:
The address of the slave cannot set to 0.
1
○