Goodrive350 series high-performance multifunction VFD
Installation guidelines
-23-
4.3 Standard wiring of main circuit
4.3.1 Wiring diagram of main circuit for a single product
37kW and lower
45
–
110kW (inclusive)
132kW and higher
Braking resistor
Braking unit
Braking resistor
Braking resistor
Braking unit
Input
reactor
Input
filter
Fuse
Input
reactor
Input
filter
3PH 380V(-15%)
–
440V(+10%)
50/60Hz
R
S
T
R
S
T
U
V
W
PE
U
V
W
PE
Output
reactor
Output
filter
M
(
+
) (
-
)
P1
(
+
)
(
-
)
PB
Fuse
Fuse
R
S
T
U
V
W
PE
Output
reactor
Output
filter
M
M
(
+
) (
-
)
DC+
DC-
DC+
DC-
DC reactor
Output
reactor
Output
filter
Input
reactor
Input
filter
3PH 380V(-15%)
–
440V(+10%)
50/60Hz
3PH 380V(-15%)
–
440V(+10%)
50/60Hz
Figure 4-7 Main circuit wiring diagram for AC 3PH 380V(-15%)
–440V(+10%)
Note:
The fuse, DC reactor, braking unit, braking resistor, input reactor, input filter, output reactor and
output filter are optional parts. See Appendix D Optional peripheral accessories.
P1 and (+) have been short connected by default for the 380V 132kW and higher VFD models. If
you need to connect to an external DC reactor, remove the jumper between P1 and (+).
Before connecting the braking resistor, remove the yellow warning sign marked with PB, (+) and
(-) on the terminal block before connecting the braking resistor wire; otherwise, poor contact may
occur.
Built-in braking units are optional for the 380V 45kW
–110kW VFD models.