Goodrive100-PV Series Solar Pumping VFD Function parameters
41
Function
code
Name
Detailed illustration of parameters
Default Modify
Full water alarm (A-tF)
Water-empty alarm (A-tL)
P08 Group Enhanced functions
P08.28
Times of fault
reset
0–10
5
○
P08.29
Interval time of
automatic fault
reset
0.1–3600.0s
10.0s
○
6.2 Parameters of special functions
Function
code
Name
Detailed illustration of parameters
Default Modify
P11 Group Protective parameters
P11.00
Phase loss
protection
0x000–0x011
LED ones:
0: Input phase loss software protection
disabled
1: Input phase loss software protection
enabled
LED tens:
0:
Output
phase
loss
software
protection disabled
1:
Output
phase
loss
software
protection enabled
LED hundreds:
Reserved
000–111
Depend
on model
○
P11.01
Frequency
decrease at
0: Disable
1: Enable
0
○