Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-91-
Function
code
Name
Description
Default
P28.26
AO1 output current
setting
0.00
–20.00mA
1.00mA
5.6.12 Digital input
The inverter unit carries four programmable digital input terminals. The function of all the digital input terminals can be
programmed through function codes.
S1
S2
S3
S4
P05.08 (Polarity of the input terminal)
P05.01
P05.02
P05.03
P05.04
T delay
T delay
T delay
T delay
P05.13
P05.15
P05.17
P05.19
0
1
2
3
4
5
.
.
.
29
30
P05.09 (Digital filter time)
(Default value is 1)
(Default value is 4)
(Default value is 7)
(Default value is 0)
0
1 -1
0
1 -1
0
1 -1
0
1 -1
P17.11
Digital input
terminal state
P07.37
Digital input
terminal state
of present fault
Fault?
Fault
Run
Digital function selection
T delay
T delay
T delay
T delay
P05.12
P05.14
P05.16
P05.18
The function parameters P05.01
–P05.04 are used to set the functions of digital multi-function input terminals.
Note: Two different multifunction input terminals cannot be configured with a same function.
Setting
Function
Description
0
No function
The inverter unit does not act even if there is signal input. Set
unused terminals without functions to avoid misaction.
1
Run forward (FWD)
External terminals are used to control the forward/reverse running
of the inverter unit.l
2
Run reversely (FWD)
3
3: Three-wire running control
The terminal is used to determine the three-wire running control of
the inverter unit. For details, see P05.13.
4
Jog forward
For details about frequency of jogging running and ACC/DEC time
of jogging running, see the description for P08.06, P08.07, and
P08.08.
5
Jog reversely
6
Jog forward
The inverter unit blocks output, and the motor stop process is
uncontrolled by the inverter unit. This mode is applied in the
scenarios with large-inertia loads and without stop time
requirements.
Its definition is the same as P01.08, and it is mainly used in remote
control.
7
Fault reset
External fault reset function, which is the same as the reset
function implemented by pressing the DATA key on the keypad.
You can use this function to reset faults remotely.
8
Pause running
The inverter unit decelerates to stop, however, all the run
parameters are in memory state, such as PLC parameter,
wobbling frequency, and PID parameter. After this signal
disappears, the inverter unit restores to the state before the stop.
9
External fault input
When an external fault signal is transmitted to the inverter unit, the
inverter unit reports a fault and stops.
10
Increase frequency setting
(UP)
Used to change the frequency increase/decrease command when
the frequency is given by external terminals.