5.6.20 Fault handling
The following describes how to handle inverter unit faults.
In running
A fault occurs.
The keypad displays the
fault code
Find out the fault
cause based on the
fault code.
Find out the most possible
cause according to P07.33
–
P07.40.
Run again.
Proper running
Remove the
fault based on the
solution.
Consult us.
Y
N
N
Y
Related parameter list:
Function
code
Name
Description
Default
P07.27
Type of present fault
0: No fault
1: Inverter unit U-phase protection (OUt1)
2: Inverter unit V-phase protection (OUt2)
3: Inverter unit W-phase protection (OUt3)
4: Overcurrent during acceleration (OC1)
5: Overcurrent during deceleration (OC2)
6: Overcurrent during constant speed running (OC3)
7: Overvoltage during acceleration (OV1)
8: Overvoltage during deceleration (OV2)
9: Overvoltage during constant speed running (OV3)
10: Bus undervoltage fault (UV)
11: Motor overload (OL1)
12: Inverter unit overload (OL2)
13: CAN fault in master/slave synchronization
(SECAN)
14: Phase loss on output side (SPO)
15: Reserved
16: Inverter module overheat (OH2)
0
P07.28
Last fault type
/
P07.29
2nd-last fault type
/
P07.30
3rd-last fault type
/
P07.31
4th-last fault type
/
P07.32
5th-last fault type
/