Goodrive600 series high-performance multifunction VFD
Basic operation guidelines
-100-
5.6.14 Simple PLC
Simple PLC is a multi-step speed generator, and the inverter unit can change the running frequency and direction
automatically based on the run time to fulfill process requirements. Previously, such function was realized with external
PLC, while now, the inverter unit itself can achieve this function.
The inverter unit can realize 16-step speed control, and provide four groups of ACC/DEC time for you to choose.
After the set PLC completes one cycle (or one step), one ON signal can be output by the multifunction relay.
Setup of running
parameters of each
PLC stage
Restart running
after the first
section
Continue running at
the frequency when
interruption occurred
Stop after running
once
Keep running in the
final value after
running once
Cyclic running
0
1
2
P10.00 (simple PLC mode)
PLC mode
0
1
0
1
0
1
Normal running
P10.01 (simple PLC memory selection)
No memory
after power off
Memory after
power off
P10.36
(PLC restart mode)
P17.00
Power off during
running
Terminal function 23
Simple PLC stop reset
Set frequency
Digital output 16
Simple PLC state completed
Digital output 17
Simple PLC cycle completed
Related parameter list:
Function code
Name
Description
Default
P05.01
–P05.04
Digital input function
selection
23: Simple PLC stop reset
24: Pause simple PLC
25: Pause PID control
/
P06.01
–P06.04
Digital output function
selection
16: Simple PLC stage reached
17: Simple PLC cycle reached
/
P10.00
Simple PLC mode
0: Stop after running once
1: Keep running in the final value after
running once
2: Cyclic running
0
P10.01
Simple PLC memory
selection
0: No memory after power off
1: Memory after power off
0
P10.02
Multi-step speed 0
-100.0
–100.0%
0.0%
P10.03
Running time of step 0
0.0
–6553.5s (min)
0.0s
P10.04
Multi-step speed 1
-100.0
–100.0%
0.0%
P10.05
Running time of step 1
0.0
–6553.5s (min)
0.0s
P10.06
Multi-step speed 2
-100.0
–100.0%
0.0%
P10.07
Running time of step 2 0.0
–6553.5s (min)
0.0s
P10.08
Multi-step speed 3
-100.0
–100.0%
0.0%
P10.09
Running time of step 3
0.0
–6553.5s (min)
0.0s
P10.10
Multi-step speed 4
-100.0
–100.0%
0.0%
P10.11
Running time of step 4
0.0
–6553.5s (min)
0.0s
P10.12
Multi-step speed 5
-100.0
–100.0%
0.0%