EMC. The assembler is responsible for ensuring that the end
product or system complies with all the relevant laws in the
country where it is to be used.
WARNING:
Fire hazard. Suitable for mounting on concrete or other
non-combustible surface only.
WARNING:
Be aware that the input DC voltage of the INVOLAR
Micro-Inverter shall not exceed 50V, higher voltage may
cause permanent damage to the device; it contains no user
serviceable and INVOLAR-Micro-Inverter Warranty parts.
WARNING:
This unit is not provided with a GFDI device. The inverter must
be fitted with an external device as required by the Article 690
of the National Electrical Code for the Installation location.
WARNING:
The device is not provided with automatic disconnecting
means – this device shall be provided with external relaying
protection in accordance with local codes and local utility
requirements.
WARNING:
To reduce the risk of fire, do not connect to an ac load centre
(circuit breaker panel) having multi-wire branch circuits
connected
CAUTION:
To reduce the risk of fire, connect only to a circuit provided
with 16 amperes maximum branch-circuit overcurrent
protection in accordance with local codes and local utility
requirements.
CAUTION:
Final circuit over current protection of the AC circuit shall be
provided by others and should be suitable for system design.
EC Directives
This chapter follows the requirements of the European Low Voltage
Directives,contains the safety instructions and conditions of acceptability for the
standard, which you must follow when installing, operating and servicing the unit. If