background image

Optidrive ODE-2 User Guide Revision 3.20 

28 

www.invertekdrives.com 

 

 

10

 

Tr

o

u

b

le

 Sh

oo

ti

n

10.

 

Trouble Shooting 

10.1.

 

Fault Code Messages 

Display 

Fault Code 

Fault 

Number 

Description 

Corrective Action 



0x00 

Drive is healthy and in a stopped condition. The motor is not energised. No enable signal is present to start the drive 



0X0A 

Factory Default parameters 
have been loaded 

Press the STOP key, drive is ready to configure for particular application 



0x03 

Instantaneous Over current 
on the drive output.  
Excess load or shock load on 
the motor. 

Fault occurs immediately on drive enable or run command 

Check the output wiring connections to the motor and the motor for short circuits phase 
to phase and phase to earth. 

Fault occurs during motor starting 

Check the motor is free to rotate and there are no mechanical blockages. If the motor has 
a brake fitted, check the brake is releasing correctly. Check for the correct star-delta 
motor wiring. Ensure the motor nameplate current is correctly entered in P-08. Increase 
the acceleration time in P-03. Reduce the motor boost voltage setting in P-11 

Fault occurs when motor operating at constant speed 

Investigate overload or malfunction.  

Fault occurs during motor acceleration or deceleration

  

The Accel/Decel times are too short requiring too much power. If P-03 or P-04 cannot be 
increased, a bigger drive may be required 



0x04 

Motor thermal overload 
protection trip. The drive 
has tripped after delivering 
>100% of value in P-08 for a 
period of time to prevent 
damage to the motor. 

Ensure the correct motor nameplate current value is entered in P-08. Check for correct 
Star or Delta wiring configuration. Check to see when the decimal points are flashing 
(which indicates the output current > P-08 value) and either increase acceleration ramp 
(P-03) or decrease motor load.  Check the total motor cable length is within the drive 
specification. Check the load mechanically to ensure it is free, and that no jams, blockages 
or other mechanical faults exist 



0x01 

Brake channel over current 
(excessive current in the 
brake resistor) 

Check the cabling to the brake resistor and the brake resistor for short circuits or damage. 
Ensure the resistance of the brake resistor is equal to or greater than the minimum value 
for the relevant drive shown in the table in section 9.2 



0x02 

Brake resistor thermal 
overload. The drive has 
tripped to prevent damage 
to the brake resistor 

Only occurs if P-34 = 1. The internal software protection for the brake resistor has 
activated to prevent damage to the brake resistor.  

If an Invertek standard braking resistor is being used, P-34 MUST be 1 

Increase the deceleration time (P-04) or 2

nd

 deceleration time (P-24). Reduce the load 

inertia 

For Other Brake Resistors 

Ensure the resistance of the brake resistor is equal to or greater than the minimum value 
for the relevant drive shown in the table in section 9.2. Use an external thermal 
protection device for the brake resistor. In this case, P-34 may be set to 2 



0x05 

Hardware Over Current 

Check the wiring to motor and the motor for phase to phase and phase to earth short 
circuits. Disconnect the motor and motor cable and retest. If the drive trips with no motor 
connected, it must be replaced and the system fully checked and retested before a 
replacement unit is installed. 

.



0x06 

Over voltage on DC bus 

Check the supply voltage is within the allowed tolerance for the drive. If the fault occurs 
on deceleration or stopping, increase the deceleration time in P-04 or install a suitable 
brake resistor and activate the dynamic braking function with P-34 

.



0x07 

Under voltage on DC bus 

The incoming supply voltage is too low. This trip occurs routinely when power is removed 
from the drive. If it occurs during running, check the incoming power supply voltage and 
all components in the power feed line to the drive. 



0x08 

Heatsink over temperature 

The drive is too hot. Check the ambient temperature around the drive is within the drive 
specification. Ensure sufficient cooling air is free to circulate around the drive.  
Increase the panel ventilation if required. Ensure sufficient cooling air can enter the drive, 
and that the bottom entry and top exit vents are not blocked or obstructed. 



0x09 

Under temperature 

Trip occurs when ambient temperature is less than -10°C.  Temperature must be raised 
over -10°C in order to start the drive. 



0x10 

Faulty thermistor on 
heatsink. 

Refer to your IDL Authorised Distributor. 



0x0B 

External trip  
(on digital Input 3) 

E-trip requested on digital input 3.  Normally closed contact has opened for some reason. 
If motor thermistor is connected check if the motor is too hot. 



0x0C 

Comms loss trip 

Check communication link between drive and external devices. Make sure each drive in 
the network has its unique address. 



0x0E 

Input phase loss trip 

Drive intended for use with a 3 phase supply has lost one input phase. 



0x0F 

Spin start failed 

Spin start function failed to detect the motor speed. 



0x11 

Internal memory fault. 

Parameters not saved, defaults reloaded. 
Try again. If problem recurs, refer to your IDL Authorised Distributor. 



0x12 

Analog input current out of 
range 

Check input current in range defined by P-16. 



Internal drive Fault 

Refer to your IDL Authorised Distributor. 



Internal drive Fault 

Refer to your IDL Authorised Distributor. 



 

82-E2MAN-IN_V3.20 

Summary of Contents for Optidrive ODE-2-11005-1H01 Series

Page 1: ...ptidrive ODE 2 User Guide Revision 3 20 www invertekdrives com 1 1 Introduction User Guide IP20 IP66 NEMA 4X AC Variable Speed Drive 0 37 11kW 0 5 15HP 110 480V Installation and Operating Instructions...

Page 2: ...13 Motor Nameplate Details Enter the motor rated voltage in P 07 Enter the motor rated current in P 08 Enter the motor rated frequency in P 09 Keypad operation can be found on page 16 Control Termina...

Page 3: ...nter the motor rated current in P 08 Enter the motor rated frequency in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse...

Page 4: ...cy in P 09 Supply Voltage 110 115 200 240 400 480 VAC 10 1 or 3 Phase Check the drive rating information on page 26 Fuses or MCB Fuse Ratings given on page 26 Recommended cable sizes shown on page 26...

Page 5: ...factors including the environment in which the drive is installed motor switching frequency motor cable lengths and installation methods adopted For shielded motor cable lengths greater than 100m and...

Page 6: ...ctions 13 4 6 Motor Thermal overload Protection 14 4 7 Control Terminal Wiring 14 4 8 Connection Diagram 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4 10 Control Terminal Conne...

Page 7: ...ses or MCB Suitably rated fuses or MCB should be fitted in the mains supply to the drive according to any local legislation or codes Do not carry out any work on the drive control cables whilst power...

Page 8: ...50 1KB4 ODE 2 22150 1K04 1 5 ODE 2 22020 1HB4 ODE 2 22020 1H04 2 7 2 ODE 2 22220 1KB4 ODE 2 22220 1K04 2 2 ODE 2 22030 1HB4 ODE 2 22030 1H04 3 10 5 2 N A ODE 2 32040 1K04 2 4 0 N A ODE 2 32050 1H04 2...

Page 9: ...97 5 5 0 22 10 0 39 1 0 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 110 4 33 63 2 48 5 5 0 22 10 0 39 1 7 3 8 3 261 10 28 246 9 69 247 9 72 6 0 24 175 6 89 131 5 16 80 3 15 5 5 0 22 1...

Page 10: ...All Frame Sizes Control Terminals 0 5 Nm 4 5 lb in Power Terminals 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmen...

Page 11: ...For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched mo...

Page 12: ...tor ground must be connected to one of the ground terminals on the drive Ground Fault Monitoring As with all inverters a leakage current to earth can exist The Optidrive is designed to produce the min...

Page 13: ...t power supply faults Part numbers are shown in the table Supply Frame Size AC Input Inductor 230 Volt 1 Phase 1 OPT 2 L1016 20 2 OPT 2 L1025 20 3 N A 400 Volt 3 Phase 2 OPT 2 L3006 20 2 OPT 2 L3010 2...

Page 14: ...s of different voltages e g 24 Volt DC and 110 Volt AC should not be routed in the same cable Maximum control terminal tightening torque is 0 5Nm Control Cable entry conductor size 0 05 2 5mm2 30 12 A...

Page 15: ...un in PI Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Pres...

Page 16: ...turned to minimum 5 Turn the potentiometer to maximum The motor will accelerate to 50Hz the default value of P 01 under the control of the accelerating ramp time P 03 The display shows 50Hz at max sp...

Page 17: ...the motor P 10 Motor Rated Speed 0 30000 0 Rpm This parameter can optionally be set to the rated nameplate rpm of the motor When set to the default value of zero all speed related parameters are displ...

Page 18: ...1 0 0 Hz Rpm P 21 Preset Frequency Speed 2 P 02 P 01 0 0 Hz Rpm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected...

Page 19: ...ut Software Protection Enables the internal brake chopper without software protection An external thermal protection device should be fitted P 35 Analog Input 1 Scaling 0 0 500 0 100 0 Scales the anal...

Page 20: ...erence between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops suffi...

Page 21: ...y This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain operat...

Page 22: ...e or similar to digital input 3 7 Open Stop disable Closed Fwd Run enable Open Stop disable Closed Rev Run enable External trip input Open Trip Closed Run Analog input 1 reference Closing digital inpu...

Page 23: ...ton Open Keypad speed ref 24V Preset speed 1 3 1 Open Stop disable Closed Run enable Closed remote UP push button External trip input Open Trip Closed Run Closed remote DOWN push button Connect extern...

Page 24: ...trip input Open Trip Closed Run PI feedback analog input Connect external motor thermistor PTC type or similar to digital input 3 4 Normally Open NO Momentary close to run Normally Closed NC Momentary...

Page 25: ...2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Checksum...

Page 26: ...0 75 1 8 5 16 10 1 5 14 4 3 1 5 14 50 N A 1 1 5 2 13 9 25 20 2 5 12 7 1 5 14 50 N A 2 1 5 2 15 2 25 20 2 5 12 7 1 5 14 100 100 2 2 2 3 19 5 25 25 4 10 10 5 1 5 14 100 50 3 4 5 30 5 40 40 4 8 16 2 5 12...

Page 27: ...recommends the installation of input line reactors Frequency 50 60Hz 5 Variation Short Circuit Capacity Voltage Rating Min kW HP Max kW HP Maximum supply short circuit current 115V 0 37 0 5 1 1 1 5 5...

Page 28: ...vertek standard braking resistor is being used P 34 MUST be 1 Increase the deceleration time P 04 or 2nd deceleration time P 24 Reduce the load inertia For Other Brake Resistors Ensure the resistance...

Reviews: