Optidrive P2 Elevator User Guide V2.30
37
Start-up of Gearless (Permanent Magnet) Motor-With Encoder Feedback.
www.InvertekDrives.com
12.
Start-up of Gearless (Permanent Magnet) Motor-With Encoder Feedback.
The below procedure illustrates a method for commissioning the OPTIDRIVE P2 ELEVATOR drive in a typical elevator application, it is assumed
the drive has already been mechanically installed.
Step 1- Wiring Connections.
The below diagram provides guidance for the wiring connections.
More technical information on the electrical wiring is available in section 6 “Electrical Installation” and section 18 “Technical Data”.
Before making any wiring connections ensure that all voltage/power sources are isolated.
Step 1- Wiring Connection diagram.
Optidrive
Elevator
L3
L2
L1
3 Phase mains input.
U
V
W
Motor
Contactors
L1 L2 L3
U V W
+
Br
Braking
Resistor
+24Vdc
High Spd
Inspection spd
Up
Dn
1
4
6
2
3
Drive Inhibit(*)
12
(STO)
13
7
24Vdc Output (Drive Healthy)
Motor Contactor command
Motor Brake command
Control
Terminals
(A)
0V for 24Vdc outputs
24Vdc Output (Drive Enabled)
8
9
14
15
17
18
Relay 1
Relay 2
11
Control
Terminals
(B)
Note : Ensure that internal and
external shields of encoder cable are
connected to terminal 11.
Cable screening/Shield
For Guidance on cable screening/shielding see section 6.1 “Installation in accordance with Good EMC Practice”
Drive Inhibit (*)
From a fast relay connected downstream of the safety chain.
Control Terminals (A)
Default configuration shown, for other configurations see section 6.10.1 “Digital Input Configuration Parameter (P1-
13)”
Control Terminals (B)
Default status sources shown for digital outputs (terminal 8 and 11), for other status sources see parameters P2-11
(terminal 8 function) and P2-13
Encoder Module
For Endat Encoder use OPT-2-ENDAT2-IN module. For SinCos Encoder use OPT-2-SINCOS2-IN module.
Braking Resistor
Ensure braking resistor resistance is higher than minimum allowable value for the given drive rating, see section 18.3.