Optidrive P2 Elevator User Guide V2.30
31
Start up and Commissioning
www.InvertekDrives.com
Motor Operating Modes.
In order to support a wide range of elevator motor types and vintages the Optidrive P2 Elevator drive has 4 different operating modes, the
various operating modes are selected in parameter P4-01 and are detailed in the table below.
P4-01
Operating Mode
Application
0
Advanced Vector IM Speed Control
(With or Without Incremental Encoder
feedback)
Recommended operating mode for Induction motors.
Induction (geared) Motors where all motor data is available from the motor rating
plate/ datasheet (Motor rated Voltage/Current/Frequency/Rated rpm/Power factor).
Excellent low speed torque performance.
1
Vector IM Speed Control
(With or Without Incremental Encoder
feedback)
Alternative to setting 0 for Geared (Induction) Motors where the power factor value is
not available from the motor rating plate/ datasheet.
Low speed torque performance reduced compared to setting 0.
2
Enhanced V/F IM Speed Control
For Geared (Induction) Motors where settings 0 or 1 are not suitable for the connected
motor .e.g. older motors or where vector control (settings 0 or 1) results in motor
vibrations which cannot be tuned out by adjustment of the speed loop gains.
In this mode the speed loop gains are not active.
Low speed torque performance reduced compared to setting 0 and 1.
3
PM Motor Speed Control
(With or *Without Absolute Encoder
feedback)
Permanent magnet (gearless) Motors.
Excellent low speed torque performance and efficiency.
*PM Open Loop Vector control with Limitations (Motor dependant), contact Invertek Technical/product support for further information