7

 

7.

 

Analog and Digital Input Configurations 

7.1.

 

Terminal Mode (P-12 = 0) 

P-15 

Digital input 1 (T2) 

Digital input 2 (T3) 

Digital input 3 (T4) 

Analog input (T6) 

Comments 

Open: Stop (disable) 
Closed: Run (enable) 

No Effect 

Open : Analog speed ref 
Closed : Preset speed 1 

Analog input  1 reference 

 

Open: Stop (disable) 
Closed: Run (enable) 

Open: Analog speed ref 
Closed: Preset speed 1/2 

Open: Preset speed 1 
Closed: Preset speed 2 

Analog input  1 reference 

 

Open: Stop (disable) 
Closed: Run (enable) 

Digital Input 2 

Digital Input 3 

Preset Speed 

Open: Preset speeds 1-4 
Closed: Max Speed(P-01) 

4 Preset speeds selectable.  
Analog input used as digital 
input Closed status: 8V < Vin 
< 30V 
 

Open 

Open 

Preset Speed 1  

Closed 

Open 

Preset Speed 2 

Open 

Closed 

Preset Speed 3 

Closed 

Closed 

Preset Speed 4 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Analog speed ref 
Closed : Preset speed 1 

External trip input : 

Open: Trip,  
Closed: Run 

Analog input  1 reference 

Connect external motor 
thermistor PTC type or 
similar to  digital input 3 

Open: Stop (disable) 
Closed: Run (enable) 

Open : Analog input 1 
Closed : Analog input 2 

Analog input 2 reference  Analog input  1 reference 

Switches between analog 
inputs 1 and 2 

Open: Stop (disable) 
Closed: Run (enable) 

Open: Run 
Closed: Fast Stop 

Open : Analog speed ref 
Closed : Preset speed 1 

Analog input  1 reference 

Close digital input 2  to carry 
out a fast stop (P-24) 

Open: Stop (disable) 
Closed: Run (enable) 

No Effect 

External trip input : 

Open: Trip,  
Closed: Run 

Analog input  1 reference 

Connect external motor 
thermistor PTC type or 
similar to  digital input 3 

Open: Stop (disable) 
Closed: Run (enable) 

Open: Run 
Closed: Fast Stop 

External trip input : 

Open: Trip,  
Closed: Run 

Analog input  1 reference 

Close digital input 2  to carry 
out a fast stop (P-24), 
provided P-05=0 

Open: Stop (disable) 
Closed: Run (enable) 

No Effect 

Digital Input 3 

Analog Input 1 

Preset Speed 

 

Open 

Open 

Preset Speed 1 

Closed 

Open 

Preset Speed 2 

Open 

Closed 

Preset Speed 3 

Closed 

Closed 

Preset Speed 4 

Open: Stop (disable) 
Closed: Run (enable) 

Open: Run 
Closed: Fast Stop 

Digital Input 3 

Analog Input 1 

Preset Speed 

Close digital input 2  to carry 
out a fast stop (P-24), 
provided P-05=0 

Open 

Open 

Preset Speed 1 

Closed 

Open 

Preset Speed 2 

Open 

Closed 

Preset Speed 3 

Closed 

Closed 

Preset Speed 4 

10 

Normally Open (NO) 
Momentary close to run 

Normally  Closed (NC) 
Momentary open to stop 

Open : Analog speed ref 
Closed: Preset speed 1 

Analog input  1 reference 

 

11 

Normally Open (NO) 
Momentary close to run 

Normally  Closed (NC) 
Momentary open to stop 

Normally Open (NO) 
Momentary close to Fast 
Stop 

Analog input  1 reference 

Close digital input 3  to carry 
out a fast stop (P-24), 
provided P-05=0 

12 

Open: Stop (disable) 
Closed: Run (enable) 

Open: Fast Stop (disable) 
Closed: Run (enable) 

Open : Analog speed ref 
Closed : Preset speed 1 

Analog input  1 reference 

 

 

Typical Applications 

Terminal Mode P-12=0, P-15=0

 

Terminal Mode P-12=0, P-15 = 1

 

Terminal Mode P-12=0, P-15=2

 

 

+24 Volt 

 

+24 Volt 

 

+24 Volt 

Run (Enable) 

Run (Enable) 

Run (Enable) 

 

Analog / Preset 

Preset Speeds 1 – 4 
Select 

Analog / Preset 

Preset1 / Preset2 

+ 10 Volts 

+ 10 Volts 

 

Reference 

Reference 

Preset / Max Speed 

0 Volts 

0 Volts 

 

Analog speed input with 1 preset speed

 

Analog speed input with 2 preset speeds

 

4 preset speeds and max speed select switch.  

Effectively giving 5 preset speeds

 

 

 

Summary of Contents for ODE-2-11005-1H012-01

Page 1: ...ase Output User Guide V3 10 User Guide Single Phase Output AC Variable Speed Drive for PSC Shaded Pole Single Phase Motors 0 37 1 1kW 0 5 1 5HP IP20 Open IP66 Nema 4X Enclosed Units Installation and O...

Page 2: ...gs out of the box 1 Connect a START STOP switch from Terminal 1 to 2 Close the contact START enable the drive Open the contact STOP the drive 2 Connect a 10k potentiometer on terminal 5 6 7 to vary th...

Page 3: ...h is set to the REV position set parameter value in P 15 Check page 15 for configuring the FWD REV switch for Local Remote Hand off Auto applications Local Power Isolator with Lock off provision Fuses...

Page 4: ...motor switching frequency motor cable lengths and installation methods adopted Note For shielded motor cable lengths greater than 100m and up to 200m an output dv dt filter must be used please refer t...

Page 5: ...Wiring 13 4 7 Connection Diagram IP20 Open IP66 Nema 4X Non Switched Units 14 4 8 Connection Diagram IP66 Nema 4X Switched Units 14 4 9 Using the REV 0 FWD Selector Switch Switched Version Only 15 4...

Page 6: ...Do not carry out any work on the drive control cables whilst power is applied to the drive or to the external control circuits Within the European Union all machinery in which this product is used mu...

Page 7: ...0 1 Phase Input kW Model Number kW HP Model Number HP Output Current A Frame Size With Filter Without Filter With Filter Without Filter ODE 2 12037 1KB12 01 ODE 2 12037 1K012 01 0 37 ODE 2 12005 1HB12...

Page 8: ...162 6 38 5 0 20 123 4 84 82 3 23 50 1 97 5 5 0 22 10 0 39 1 2 2 2 221 8 70 207 8 15 137 5 39 209 8 23 5 3 0 21 150 5 91 109 4 29 63 2 48 5 5 0 22 10 0 39 1 7 3 8 Mounting Bolts All Frame Sizes 4 x M4...

Page 9: ...s 1 Nm 8 85 lb in 3 7 Guidelines for mounting IP66 Units Before mounting the drive ensure that the chosen location meets the environmental condition requirements for the drive shown in section 9 1 The...

Page 10: ...pe For conduit installations the conduit entry holes require standard opening to the required sizes specified per the NEC Not intended for rigid conduit system Power Isolator Lock Off On the switched...

Page 11: ...t 3 11 1 IP66 Nema 4X Switched Unit 3 11 2 IP66 Nema 4X Non Switched Unit Drive LED Display Keypad Local Speed Potentiometer A REV 0 FWD Selector Switch B Local Power Isolator Removable Cover Control...

Page 12: ...must comply with national and local industrial safety regulations and or electrical codes Motor Ground The motor ground must be connected to one of the ground terminals on the drive Ground Fault Monit...

Page 13: ...operation with a variable speed drive then there is no preventative measures required however if the quality of insulation is unknown then the motor manufacturer should be consulted and preventative m...

Page 14: ...2 Default No Function 4 Digital Input 3 Default Analog Preset Speed 5 10 Volt Output 6 Analog Input 1 Default 0 10 Volt 7 0 Volt 8 Analog Output Default 0 10 Volts 9 0 Volt 10 Relay Output Default Dri...

Page 15: ...I Control 5 1 In Speed Control the speed is controlled from the Local POT In PI Control Local POT controls PI set point Run in Preset Speed Control STOP Run in PI Control 5 0 2 4 5 8 12 In Preset Spee...

Page 16: ...will show 4 Close the control switch terminals 1 2 The drive is now enabled and the output frequency speed are controlled by the potentiometer The display shows zero speed in Hz with the potentiometer...

Page 17: ...et the Boost Period Duration P 33 to the maximum allowed value of 150 seconds 5 Start the drive and display the motor current press the Navigate button until the display shows x x where x is the motor...

Page 18: ...en set to the default value of zero all speed related parameters are displayed in Hz and the slip compensation for the motor is disabled Entering the value from the motor nameplate enables the slip co...

Page 19: ...pm P 22 Preset Frequency Speed 3 P 02 P 01 0 0 Hz Rpm P 23 Preset Frequency Speed 4 P 02 P 01 0 0 Hz Rpm Preset Speeds Frequencies selected by digital inputs depending on the setting of P 15 If P 10 0...

Page 20: ...a 0 10V signal and the scaling factor is set to 200 0 a 5 volt input will result in the drive running at maximum frequency speed P 01 P 36 Serial Communications Configuration See Below This parameter...

Page 21: ...nce between the setpoint and feedback for which the drive will remain in Standby Mode This allows the drive to ignore small feedback errors and remain in Standby mode until the feedback drops sufficie...

Page 22: ...uency This value maybe lower than the selected frequency in P 17 if the drive is too hot The drive will automatically reduce the switching frequency to prevent an over temperature trip and maintain op...

Page 23: ...ence Connect external motor thermistor PTC type or similar to digital input 3 7 Open Stop disable Closed Run enable Open Run Closed Fast Stop External trip input Open Trip Closed Run Analog input 1 re...

Page 24: ...orward Run Open Run Closed Fast Stop External trip input Open Trip Closed Run Open Keypad speed ref 24V Preset speed 1 Close digital input 3 to carry out a fast stop P 24 provided P 05 0 Example Wirin...

Page 25: ...Run Enable Run Enable Run Enable PI Preset Speed 1 PI Local Hand PI Preset Speed 1 PI Feedback PI Feedback External Trip 10 Volt Local Hand Ref PI Feedback 0 Volt 0 Volt 0 Volt Remote closed loop PI f...

Page 26: ...ress 2 Bytes Register Address 2 Bytes No Of Registers 2 Bytes 2 nd Register Value 2 Bytes Value 2 Bytes Register Value 2 Bytes CRC Checksum 2 Bytes Etc CRC Checksum 2 Bytes CRC Checksum 2 Bytes CRC Ch...

Page 27: ...s for 230 Volt rated units 10 variation allowed 240 Volt RMS Maximum Imbalance Maximum 3 voltage variation between phase phase voltages allowed All Optidrive E2 units have phase imbalance monitoring A...

Page 28: ...eration time reduce load inertia or add further brake resistors in parallel Ensure minimum resistance values form the rating tables are observed Internal power stage fault Check wiring to motor look f...

Reviews: