66
| Optidrive Eco User Guide |
Version 3.07
www.invertekdrives.com
11. Technical Data
11.1. Environmental
Ambient Temperature Range
Storage
All
-40 °C … 60 °C
Operational
IP20
-10 … 50°C without derating
IP55
-10 … 40°C without derating
IP66
Maximum Altitude
Operational
All
1000m without derating
Relative Humidity
Operational
All
=< 95% (no condensation permitted)
11.8. Derating Information on page 72
for derating information.
11.2. Input Power Supply Requirements
Input Power Supply Requirements
Supply Voltage
200 – 240 RMS Volts for 230 Volt rated units, + /- 10% variation allowed.
380 – 480 RMS Volts for 400 Volt rated units, + / - 10% variation allowed.
500 – 600 RMS Volts for 600 Volt rated units, + / - 10% variation allowed.
Imbalance
Maximum 3% voltage variation between phase – phase voltages allowed.
All Optidrive Eco units have phase imbalance monitoring. A phase imbalance of > 3% will result in the
drive tripping.
Frequency
50 – 60Hz + / - 5% Variation.
11.3. Input Voltage Ranges
Depending upon model and power rating, the drives are designed for direct connection to the following supplies:
Model Number
Supply Voltage
Phases
Frequency
ODV-3-x2xxxx-1xxx-xx
200 – 240 Volts + / - 10%
1
50 – 60 Hz
ODV-3-x2xxxx-3xxx-xx
200 – 240 Volts + / - 10%
3
50 – 60 Hz
ODV-3-x4xxxx-3xxx-xx
380 – 480 Volts + / -10%
3
50 – 60 Hz
ODV-3-x6xxxx-3xxx-xx
500 – 600 Volts + / - 10%
3
50 – 60 Hz
11.4. Phase Imbalance
All three phase Optidrive Eco units have phase imbalance monitoring. The maximum permissible voltage imbalance between any two
phases is 3% for full load operation.
11.5. Output Power and Current ratings
The following tables provide the output current rating information for the various Optidrive Eco models. Invertek Drives always
recommend that selection of the correct Optidrive is based upon the motor full load current at the incoming supply voltage.
Please note that the maximum cable length stated in the following tables indicate the maximum permissible cable length for the drive
hardware and does not take into consideration EMC compliance.
11