background image

AC 230 V, 50 Hz
DC 24 V

DC 24 V

Outputs Clust-Air module

:

Control BUS:    DC 24 V, 4-pole
Fan BUS:  

  

          DC 6.8 V – 15.3 V, 3-pole

Analogue input: 

 

Control cable DC 0 V –10 V / Resolution 10 Bit

External switching contact:   Floating

IP20

i

Installation and operating instructions MZ-One (05/16)

AC

DC

3

3

3

4

4

4

4

3

4

4

4

4

DC 24 V

L

PE

N

+

A

B

+

A

B

+

A

B

+

+

+

+

AC 230 V, 50 Hz

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

+

A

+

A

+

A

+

+

+

+

+

J-Y(ST)Y

-2x2x0.8 / Max.: 200 m

J-Y(ST)Y-2x2x0.8 / Max.: 15 m 

 

LiYY3x0.75 / Max.: 10 m 

 

+

B A

+

+

A

B

+

A

B

A

+

Wire: 2x1.5 

A

+

A

+

A

+

B

A

+

+

Rear side:
PCB of programming unit

Front view:
Clust-Air module

B

+

A

NC

NC

A

+

NC

NC

NC

NC

NC

NC

Cable cross-sections and maximum cable lengths

 Control BUS:   

 Cable cross-section:  

   0.25 mm

2

 – 0.5 mm

2

 

 Cable J-Y(ST)Y-2x2x0.8:    DC 24 V
 Maximum cable length:     200 m

 Fan BUS:

  

 Cable cross-section: 

   Min. 0.75 mm

2

 Cable LiYY3x0.75:  

   DC 6.8 V – 15.3 V

 Maximum cable lengths:    Clust-Air module to 2 – 4 ventilation units iV12-Smart/iV14: 

Max. 33 m each (star-shaped)

 

   

   Clust-Air module to 4 ventilation units iV12-Smart/iV14:   

Max. 10 m (sequentially)

 

   

   Clust-Air module to 2 ventilation units iV12-Smart/iV14:   

Max. 20 m (sequentially)

 

                Clust-Air module to 1 – 2 ventilation units iV25/iV-Twin:   

Max. 20 m each (star-shaped)

 

   

   Clust-Air module to 1 ventilation unit iV-Twin: 

 

 

Max. 10 m (sequentially)

 Temperature-humidity  sensor: 

 

 Cable cross-section: 

0.25 mm

2

 – 0.5 mm

2

 Cable J-Y(ST)Y-2x2x0.8:  DC 5 V
 Maximum cable length: 

15 m

MZ-One

®

 

Electrical connection

S

  

    

  

 

  

  

  

 

 

    

11.04.2016   11:55:31