background image

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

IntesisBox

®

 BACnet Server

 

M-Bus Meters 

 
 

 
 
 
 
 
 
 
 
 

 

User Manual

 

r1.0 eng 

Issue date: 

09/2017 

 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

 

Summary of Contents for IBBACMEB0100000

Page 1: ...IntesisBox BACnet Server M Bus Meters User Manual r1 0 eng Issue date 09 2017...

Page 2: ...icense agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval system or...

Page 3: ...All rights reserved IntesisBox is a registered trademark of Intesis Software SLU 3 41 Gateway for the integration of M Bus devices into BACnet MSTP or BACnet IP enabled monitoring and control systems...

Page 4: ...operties 16 5 2 1 IBOX BAC MBM Device Object Type 16 5 2 2 Analog Input Object Type 18 5 2 3 Analog Output Object Type 19 5 2 4 Analog Value Object Type 20 5 2 5 Binary Input Object Type 21 5 2 6 Bina...

Page 5: ...M Bus User Manual r1 0 eng URL email tel http www intesisbox com info intesisbox com 34 938047134 Intesis Software S L U All rights reserved IntesisBox is a registered trademark of Intesis Software S...

Page 6: ...e own BACnet system and vice versa The gateway acts as a BACnet IP Server or BACnet MSTP device in its BACnet interface allowing other BACnet devices to perform subscription COV requests and reads wri...

Page 7: ...of IntesisBox Embedded level converter Direct connection to M Bus devices with no extra hardware required Scan option to automatically detect M Bus devices and its available registers Import Export of...

Page 8: ...TP Number of BACnet Objecs 250 500 1500 3000 Maximum number of points that can be defined in the virtual BACnet device inside the gateway Number of BACnet Subscriptions COV requests 500 1000 3000 6000...

Page 9: ...evice Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Specific Controller B ASC BACnet Smart Sensor B...

Page 10: ...tions Router Clause 6 List all routing configurations e g ARCNET Ethernet Ethernet MS TP etc Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support re...

Page 11: ...firmedCOVNotification DS COVP A Data Sharing COVP A SubscribeCOVProperty ConfirmedCOVNotification UnconfirmedCOVNotification DS COVP B Data Sharing COVP B SubscribeCOVProperty ConfirmedCOVNotification...

Page 12: ...ewing and Modifying Trends Inernal B ReadRange T VMT E B Trending Viewing and Modifying Trends External B ReadRange T ATR A Trending Automated Trend Retrieval A ConfirmedEventNotification ReadRange T...

Page 13: ...nfirmedTextMessage UnconfirmedTextMessage DM TS A Device Management TimeSynchronization A TimeSynchronization DM TS B Device Management TimeSynchronization B TimeSynchronization DM UTC A Device Manage...

Page 14: ...tomicWriteFile Object Access Services AddListElement RemoveListElement CreateObject DeleteObject ReadProperty ReadPropertyConditional ReadPropertyMultiple ReadRange WriteProperty WritePropertyMultiple...

Page 15: ...Types The objects supported are shown in the table below Object Type ID Supported Management Point Analog Input 0 Analog Output 1 Analog Value 2 Averaging 18 Binary Input 3 Binary Output 4 Binary Valu...

Page 16: ...tion CharacterString O Description CharacterString M Bus to BACnet Gateway O Protocol_Version Unsigned 1 R R Protocol_Revision Unsigned 12 R R Protocol_Services_ Supported BACnetServiceSupported Refer...

Page 17: ...tamp O Backup_Failure_Timeout Unsigned16 O Active_COV_ Subscriptions List of BACnetCOVSubscription List of BACnetCOVSubscription O R Slave_Proxy_Enable BACnetArray N of BOOLEAN O Manual_Slave_Address_...

Page 18: ...Flags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Update_...

Page 19: ...entState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units BACnetEngineeringUnits Configurable through BACnet a...

Page 20: ...gs FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Update_Interval Unsigned O Units B...

Page 21: ...netEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIABLE_OTHER 7 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterS...

Page 22: ...TED 0 O R Out_Of_Service BOOLEAN FALSE R R Polarity BACnetPolarity NORMAL 0 R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable t...

Page 23: ...ETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Inactive_Text CharacterString Configurable through BACnet and Config Tool O R Active_Text CharacterString Configurable through BACnet and Config Tool O R...

Page 24: ...Device_Type CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE TRUE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 UNRELIA...

Page 25: ...CharacterString O Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEA...

Page 26: ...Status_Flags BACnetStatusFlags FALSE FALSE FALSE FALSE R R Event_State BACnetEventState STATE_NORMAL 0 R R Reliability BACnetReliability NO_FAULT_DETECTED 0 O R Out_Of_Service BOOLEAN FALSE R R Numbe...

Page 27: ...27 41 5 2 11 Calendar Object Type Property Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Calendar 6 R R Object_Name CharacterString Configurable through BACne...

Page 28: ...CnetARRAY 7 of BACnetDailySchedule R W Exception_Schedule BACnetARRAY N of BACnetSpecialEvent R W Schedule_Default Any R W List_Of_Object_Property_Refer ences BACnetLIST of BACnetDeviceObjectProper ty...

Page 29: ...erty Identifier Property Datatype Value ASHRAE IBOX Object_Identifier BACnetObjectIdentifier Notification_Class 15 R R Object_Name CharacterString Configurable through BACnet and Config Tool R R Objec...

Page 30: ...PropertyReference O Log_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log_Buffer List of BACnetL...

Page 31: ...f BACnetDeviceObject PropertyReference O R Log_Interval Unsigned O COV_Resubscription_Interval Unsigned O Client_COV_Increment BACnetClientCOV O Stop_When_Full BOOLEAN R R Buffer_Size Unsigned R R Log...

Page 32: ...ontact the network administrator and make sure traffic on the port used is allowed through all the LAN path check the gateway user manual for more information Default IP is 192 168 100 246 DHCP is ena...

Page 33: ...used shall be a straight Ethernet UTP FTP CAT5 cable In case there is no response from the BACnet devices to the frames sent by IntesisBox check that they are operative and reachable from the network...

Page 34: ...M Bus level converter as well In case there is no response from the M Bus device s to the frames sent by IntesisBox check that they are operative and reachable from the network connection used by Inte...

Page 35: ...integration are IntesisBox gateway Link to download the configuration tool Product documentation IntesisBox MAPS Configuration monitoring tool for IntesisBox BACnet series 7 2 1 Introduction IntesisB...

Page 36: ...eters Three subsets of information are shown in this window General Gateway general parameters BACnet Server BACnet interface configuration and Modbus Master Modbus interface parameters Figure 7 2 Int...

Page 37: ...can be monitored in the IntesisBox Communication Console window IntesisBox will reboot automatically once the new configuration is loaded Figure 7 4 IntesisBox MAPS Receive Send tab After any configur...

Page 38: ...w intesisbox com info intesisbox com 34 938047134 Intesis Software S L U All rights reserved IntesisBox is a registered trademark of Intesis Software SLU 38 41 Figure 7 5 Diagnostic More information a...

Page 39: ...voltage applied WARNING In order to avoid earth loops that can damage IntesisBox and or any other equipment connected to it we strongly recommend The use of DC power supplies floating or with the nega...

Page 40: ...crew terminal block 3 poles 9 to 36VDC 10 Max 140mA 24VAC 10 50 60Hz Max 127mA Recommended 24VDC Push Button Button A Check the user manual Button B Check the user manual Operation Temperature 0 C to...

Page 41: ...8047134 Intesis Software S L U All rights reserved IntesisBox is a registered trademark of Intesis Software SLU 41 41 9 Dimensions Recommended available space for its installation into a cabinet wall...