IntesisBox

®

 BACnet/IP Server – DALI

 

 

Installation Manual

 

 

 

 

 

The information in this document may change without  previous notice.

 

Doc. Rev.1 

 

 

URL 

email 

tel 

 
 

http://www.intesis.com                                          
[email protected] 
+34 938047134

 

 

1 / 5

 

 

 

 

Safety Instructions

 

 

 
 

 

WARNING 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Installation Instructions

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

Configuration and Setup

 

 

 
 
Use the software LinkBoxBacnet to configure IntesisBox. Follow User’s Manual instructions for detail on the configuration process. 
 

See instructions to download and install the latest version of LinkBoxBacnet and 
its user's manual at  
 

 

http://www.intesis.com/down/bacnet/linkboxbacnet.html

 

 

 
 
 
 
 

 

IntesisBox  must  be  installed  by  accredited  electrician  or  similar  technical  personnel,  following  all  the  safety  instructions 
given here, and in accordance always with the country legislation for installation of electric equipment. 

 

IntesisBox can not be installed outdoors or exposed to direct solar radiation, water, high relative humidity or dust. 

 

IntesisBox must only be installed in a restricted access location.  

 

In case of wall mount, fix firmly IntesisBox on a not vibrating surface following the instructions below. 

 

In case of DIN rail mount fix IntesisBox properly to the DIN rail following the instructions below.  

 

Mounting on DIN rail inside a metallic cabinet properly connected to earth is recommended. 

 

Disconnect always power of any wires before manipulating and connecting them to IntesisBox.  

 

Respect always the expected polarity of power and communication cables when connecting them to IntesisBox.  

 

Supply always a correct voltage to power IntesisBox, within voltage range admitted (/ -10%).  

 

This device was designed for installation in an enclosure. To avoid electrostatic discharge to the unit in environments with 
static levels above 4 kV precautions should be taken when the device is mounted outside an enclosure. When working in 
an  enclosure  (ex.  making  adjustments,  setting    switches  etc.)  typical  anti-static  precautions  should be  observed  before 
touching the unit 

Follow  carefully  this  safety  and  installation  instructions.  Improper  work  may  lead  to  serious  harmful  for  your 
health and also may damage seriously the IntesisBox and/or any other equipment connected to it. 

 

Disconnect the mains power and power of any bus or communication cable before connecting it to IntesisBox. 

 

Mount  IntesisBox  on  the  wall  or  DIN  rail  following  the  instruction  given  below,  respecting  the  safety  instructions  given 
above. 

 

Connect the mains power cable to the supply voltage terminal block of IntesisBox. 

 

Circuit-breaker must be used before the mains power cable. Rating 250V-6A 

 

Connect the communication cables to IntesisBox, see details on the user's manual. 

 

Power IntesisBox and the rest of devices connected to it. 

 

After power-on, DALI bus LED (at the left side of DALI connector) should be ON, signalling that there is DALI bus voltage. 
If DALI bus LED is OFF, you should check the DALI communication line for a possible short-circuit. 

 

If your DALI installation is already operative, communication at DALI side can be tested by pressing the DALI test button: 

 

Pressing once the button, the ballasts will switch ON (DALI led will start flashing) 

 

Pressing again the button, the ballasts will switch OFF (DALI  led will toggle to ON) 

 

Pressing again the button, the ballasts will switch ON, and remain ON until their value is changed from BACnet side 
(DALI led will toggle to OFF, signaling that the test has ended). 

 