ASCII interface 

This section describes the ASCII interface of the IntesisBox, its configuration and functionality. 
 
 

3.1  Description 

 
The gateway can be connected to any 

ASCII enabled

 device using its EIA232 interface (DB9 connector DTE), EIA485 

interface or TCP/IP (Ethernet connector) and offers through this interface the possibility of supervision and control of its 
internal KNX addresses using simple ASCII messages.  
 
On receiving messages corresponding to write commands in its ASCII interface, the gateway sends the corresponding 
write command message to the associated KNX group. 
 
When a new value for a point is received from KNX, the corresponding ASCII message indicating the new value will be 
sent through the ASCII interface, but only if the point is configured for sending this "spontaneous messages", if it is not 
configured to do so, then the new value will be available to be polled in any moment from the ASCII enabled device 
connected to this ASCII interface. This behaviour of sending or not through the ASCII interface the new values received 
from KNX is configurable individually per point in the gateway. 
 
 

3.2  ASCII Serial 

 
Serial communication for the ASCII communication can be configured to match the ASCII master device. 
 
Only the RX, TX and GND lines of the EIA232 connector are used (TX/RX+ and TX/RX- for EIA485). 
 
 

3.3  ASCII TCP 

 
The TCP port to use can be configured (by default 5000 is used). 
 
The IP address, subnet mask and default router address to use by IntesisBox can be also configured. 
 

 

3.4  Address Map 

 
The ASCII address map is fully configurable; any point in the IntesisBox can be freely configured with the desired internal 
register address. Check the configuration tool manual for more information. 
 
 

3.5  Points definition 

 
Every point defined in the gateway has the following ASCII features associated to it, which can be configured: 
 

Feature 

Description 

Signal 

Signal or point description. Only for information purposes at user level. 

ASCII string 

Defines the ASCII string that will be used to access this register 

 

Max length: 32 characters 

 

Summary of Contents for IntesisBox ASCII

Page 1: ...IntesisBox ASCII Server KNX User Manual r1 0 EN Issue date 03 2019...

Page 2: ...se agreement or nondisclosure agreement The software may be used only in accordance with the terms of those agreements No part of this publication may be reproduced stored in a retrieval system or tra...

Page 3: ...tered trademark of Intesis Software SLU 3 20 email info intesisbox com web www intesisbox com phone 34 938047134 Gateway for the integration of KNX installations into ASCII IP or ASCII Serial enabled...

Page 4: ...CII TCP 8 3 4 Address Map 8 3 5 Points definition 8 3 6 ASCII messages 10 4 Connections 11 4 1 Powering the device 12 4 2 Connection to ASCII 12 4 2 1 ASCII TCP IP 12 4 2 2 ASCII Serial 12 4 3 Connect...

Page 5: ...m signals and resources from any system capable to be programmed to read and write simple text messages through EIA232 or EIA485 serial port or Ethernet TCP IP port for example Extron LiteTouch system...

Page 6: ...ages requesting writings of points and acts according to the message received See ASCII interface section for details about this ASCII messages Each KNX group address from the KNX is associated to an...

Page 7: ...termined by the flags configured for the point See details in section 4 2 2 Points definition Every internal datapoint to define has the following KNX properties Property Description Description Descr...

Page 8: ...is not configured to do so then the new value will be available to be polled in any moment from the ASCII enabled device connected to this ASCII interface This behaviour of sending or not through the...

Page 9: ...g to the communication object Function Read Write Read Write KNX communication object flags R T R T W U W U Ri U W Ri U R W Ri T U R W T U W T Spontaneous Determines if any change of value for the poi...

Page 10: ...gateway Character use to indicate that this is a reading message configurable from the configuration tool r Carriage return character HEX 0x0D DEC 13 Message to write a point s value ASCII_String vv r...

Page 11: ...after powering up the gateway DHCP will be enabled for 30 seconds After that time if no IP is provided by a DHCP server the default IP 192 168 100 246 will be set PortA KNX Connect the KNX TP1 bus to...

Page 12: ...communication cable coming from the ASCII network to the port marked as Port B of IntesisBox Connect the EIA485 bus to connectors to connectors B1 B B2 A and B3 SNGD of gateway s PortB Respect the pol...

Page 13: ...gateway Mini USB cable to connect to PC Link to download the configuration tool Product documentation 5 2 IntesisBox MAPS Configuration monitoring tool for IntesisBox ASCII series 5 2 1 Introduction...

Page 14: ...nfigure the connection parameters Three subsets of information are shown in this window General Gateway general parameters ASCII ASCII interface configuration and KNX KNX TP 1 interface configuration...

Page 15: ...aracter to be used to read or write the internal gateway datapoint Port TCP port to be used for the ASCII communication By default it is set to 5000 Keep Alive Time of inactivity before sending a keep...

Page 16: ...to the IntesisBox using the Send button in the Receive Send section 5 2 6 Diagnostic To help integrators in the commissioning tasks and troubleshooting the Configuration Tool offers some specific too...

Page 17: ...U All rights reserved IntesisBox is a registered trademark of Intesis Software SLU 17 20 email info intesisbox com web www intesisbox com phone 34 938047134 Figure 5 6 Diagnostic More information abou...

Page 18: ...ARNING In order to avoid earth loops that can damage IntesisBox and or any other equipment connected to it we strongly recommend The use of DC power supplies floating or with the negative terminal con...

Page 19: ...ded 24VDC Push Button Button A Reserved for future use Button B Reserved for future use Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity...

Page 20: ...stered trademark of Intesis Software SLU 20 20 email info intesisbox com web www intesisbox com phone 34 938047134 7 Dimensions Recommended available space for its installation into a cabinet wall or...

Reviews: