Operating Instructions SL MINITHERM DNLA
HOM177850763Ien-7
Page 5 / 8
INTERTEC-Hess GmbH · Raffineriestr. 8 · 93333 Neustadt/Donau · Germany ·
+49 9445 9532-0 · [email protected]
Illustration 2:
Installation example MINITHERM with TAE or TS
with clearance
Illustration 3:
nstallation example MINITHERM SL with TAE or
TS with clearance
Additional installation material, such as rails or panels
and also junction boxes, are not included in the standard
scope of delivery (see
and must be ordered additionally.
8
Connection
WARNING
The heater is only designed for non hazardous
areas.
INTERTEC-Hess GmbH accepts no liability for improper
use.
INFO
The device may only be connected up and secured by a
trained person, taking into account the "rated voltage"
and "rated current" specified on the nameplate.
Where operating voltage = measured voltage (rated
voltage), then the heater is at its rated output. Mains
voltage fluctuations up to 10 % are then permissible.
Each heater with integrated TS thermostat must be
preceded by a 10 A fuse or a motor protection switch
with short-circuit and thermal quick release (set to 10 A)
as short-circuit protection. When using a heater without
integrated thermostat, the fuse protection can be
selected according to the cross-section of the supply
cable.
In a TT or TN system, a residual current device (RCD)
must be used where the measured triggering residual
current does not exceed 100 mA. Residual current
devices with a measured triggering residual current of 30
mA are preferable. In an IT system, an insulation
monitoring device needs to be used which switches off
the supply as soon as the insulation resistance is no
greater than 50 Ω per Volt of the rated voltage.
ATTENTION:
Never remove the
adapter/ cable gland!
Illustration 4:
Example heater with KLE connection