This feature is useful considering the product only has
two relays; you can assign these relays to any of these
functions. There are only a few things to keep in mind
when assigning the outputs.
•
Any virtual output can be assigned to any physical
output.
•
A virtual output can be assigned to multiple physi-
cal outputs.
•
A physical output can only have one virtual output
assigned to it.
To assign the outputs, use the following command:
10 # virtual output # physical output # **
The chart below shows the output options with the
corresponding value.
Virtual Outputs
Physical Outputs
1 = Lock
1 = Main Relay
2 = Alarm Shunt
2 = Aux Relay
3 = Propped Door 5 = Audio Alert #1
4 = Forced Door
6 = Audio Alert #2
For example, to assign the Forced Door Output to the
Aux Relay, enter the following command in Program
mode:
10 # 4 # 2 # **
After entering this command, the Forced Door Output
is still assigned to Audio Alert #1. If you do not want
the audio alert to sound for Forced Door, you MUST
disable Audio Alert #1. To disable an output, enter a
0 for the virtual output. To disable Audio Alert #1 enter
following command:
10 # 0 # 5 # **
NOTE
: The audio alerts use the local keypad
sounder. Audio Alert #1 is indicated by a ½ second
on, ½ second off beeping. Audio Alert #2 is indi-
cated by a short beep every two seconds.