background image

14

440 04 6601 03

Specifications  subject to change without notice.

3. Remove the Main/Control door (the upper door on

upflow installations).

4. BRIEFLY (2

3 seconds) disconnect and reconnect

ONE of the main limit wires.

5. The LED will flash the last stored fault code. Refer to

the Service Label (Figure 5) to interpret the LED.

6. A component test sequence will follow.
7. Reinstall the Main/Control door.

THE BLOWER IS LOCATED

TO THE RIGHT OF THE

BURNER SECTION, AND

AIR CONDITIONED AIR IS

DISCHARGED TO THE LEFT.

THE BLOWER IS

LOCATED BELOW THE

BURNER SECTION, AND

CONDITIONED AIR IS

DISCHARGED UPWARD.

THE BLOWER IS

LOCATED ABOVE THE

BURNER SECTION, AND

CONDITIONED AIR IS

DISCHARGED DOWNWARD

THE BLOWER IS

LOCATED TO THE LEFT

OF THE BURNER SECTION,

AND CONDITIONED AIR IS

DISCHARGED TO THE RIGHT.

A02097

Figure 6 

 

Multipoise Orientations

115-V FIELD-

SUPPLIED

DISCONNECT

AUXILIARY
J-BOX

24-V

TERMINAL

BLOCK

THREE-WIRE

HEATING-ONLY

FIVE WIRE

NOTE 1

NOTE 2

FIELD-SUPPLIED
DISCONNECT

CONDENSING
UNIT

TWO
WIRE

FURNACE

C
O
N

T

R
O

L

R

G

COM

W

C

R

G

Y

GND

GND

FIELD 24-V WIRING
FIELD 115-, 208/230-, 460-V WIRING
FACTORY 24-V WIRING
FACTORY 115-V WIRING

208/230- OR
460-V
THREE
PHASE

208/230-V
SINGLE
PHASE

BLOWER DOOR SWITCH

WHT

BLK

WHT

BLK

NOTES:

Connect Y-terminal in furnace as shown for proper blower operation.
Some thermostats require a "C" terminal connection as shown.
If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.

W

Y

GND

THERMOSTAT
TERMINALS

1.
2.
3.

A11387

Figure 7 

 

Typical  Single

Stage  Wiring Diagram

Component Self-Test

NOTE

:  The furnace control component test allows all

components to run for a short time; except the gas valve

and humidifier terminal HUM are not energized. The EAC-1
terminal is energized when the blower is energized. This
feature helps diagnose a system problem in case of a

component failure. The component test feature will not

operate if any thermostat signal is present at the control and
not until all time delays are completed.
To Begin Component Self-Test:

1. Remove blower access door.
2. Disconnect the thermostat R lead from furnace

control.

3. Manually close blower door switch.

Summary of Contents for R9MSB

Page 1: ...n the following manner CAUTION Signal Words on Product Labeling Signal words are used in combination with colors and or pictures or product labels The signal word WARNING is used throughout this manua...

Page 2: ...eath WARNING signifies hazards which could result in personal injury or death CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage NOTE...

Page 3: ...115vac terminal is energized whenever blower operates HUM 24vac terminal is only energized when the low pressure switch LPS is closed on a call for heat Prime Condensate Trap with Water CARBON MONOXID...

Page 4: ...ired orifice to the manifold pressure to the heat content and specific gravity of the gas To do this 1 Obtain average yearly gas heat value at installed altitude from local gas supplier 2 Obtain avera...

Page 5: ...put is obtained replace cap that conceals gas valve regulator adjustment screws Main burner flame should be clear blue almost transparent See Figure 12 i Remove jumper R to W 2 Verify natural gas inpu...

Page 6: ...exchangers or condensing flue gases in heat exchanger areas not designed for condensate S Shortened furnace life S Component damage Temperature rise must be within limits specified on furnace rating p...

Page 7: ...nals when furnace is in low heat and after blower starts 4 Set heat anticipator on thermostat per thermostat instructions and install on sub base or wall 5 Install blower access door Electronic thermo...

Page 8: ...LE STAGE A11153 Gas Valve without Tower Pressure Ports ON OFF SWITCH 1 8 NPT INLET PRESSURE TAP REGULATOR SEAL CAP REGULATOR ADJ UNDER CAP 1 2 NPT OUTLET MANIFOLD PRESSURE TAP SET SCREW 3 32 HEX HEAD...

Page 9: ...290 22 164 327 818 64 56 112 281 23 157 313 783 66 54 109 273 24 150 300 750 68 53 106 265 25 144 288 720 70 51 103 257 26 138 277 692 72 50 100 250 27 133 267 667 74 48 97 243 28 129 257 643 76 47 9...

Page 10: ...10 440 04 6601 03 Specifications subject to change without notice 338309 201 Rev E A11602 Figure 5 Service Label Information...

Page 11: ...2 42 3 3 42 3 4 915 825 43 3 6 43 3 7 43 3 8 42 3 2 850 44 3 8 43 3 5 43 3 6 43 3 7 875 44 3 6 44 3 7 43 3 4 43 3 5 4000 900 44 3 4 44 3 5 44 3 7 44 3 8 1219 925 44 3 2 44 3 4 44 3 5 44 3 6 950 44 3...

Page 12: ...0 885 Red 3 2 5 394 1030 1025 1030 1010 985 940 905 855 805 735 0801716 SIDE BOTTOM Black 4 0 408 1800 1770 1735 1685 1630 1570 1495 1415 1330 1230 Yellow 3 5 386 1445 1430 1410 1385 1350 1305 1255 11...

Page 13: ...re switch is 0 68 in W C The minimum break point of the switch is 0 63 in W C The maximum break point of the switch is 0 73 in W C The maximum make point of the switch is 0 83 in W C ELECTRICAL SHOCK...

Page 14: ...T CONDENSING UNIT TWO WIRE FURNACE C O N T R O L R G COM W C R G Y GND GND FIELD 24 V WIRING FIELD 115 208 230 460 V WIRING FACTORY 24 V WIRING FACTORY 115 V WIRING 208 230 OR 460 V THREE PHASE 208 23...

Page 15: ...est furnace with room thermostat to be sure that it operates properly with the room thermostat Check all modes including Heat Cool and Fan 8 Check operation of accessories per manufacturer s instructi...

Page 16: ...binet 7 Replace filter cabinet door 8 Turn on electrical supply to furnace Blower Motor and Wheel Maintenance To ensure long life economy and high efficiency clean accumulated dirt and grease from blo...

Page 17: ...aning Burners and Flame Sensor The following items must be performed by a qualified service technician If the burners develop an accumulation of light dirt or dust they may be cleaned by using the fol...

Page 18: ...burner assembly without striking the igniter on surrounding parts c Inspect igniter for signs of damage or failure d If replacement is required remove the screw that secures the igniter on igniter bra...

Page 19: ...xchangers The following items must be performed by a qualified service technician Primary Heat Exchangers If the heat exchangers get an accumulation of light dirt or dust on the inside they may be cle...

Page 20: ...ed Follow these procedures to winterize your furnace UNIT COMPONENT DAMAGE HAZARD Failure to follow this caution may result in damage to the furnace and other property damage Do not use ethylene glyco...

Page 21: ...ner Manifold A11461 Figure 12 Burner Flame SET SCREW MOTOR WHEEL HUB MOTOR SHAFT FLAT SCREW MOTOR ARM GROMMET SCREW LOCATION BLO HSG ASSY BRACKET BRACKET ENGAGEMENT SEE DETAIL A CAPACITOR OR POWER CHO...

Page 22: ...22 440 04 6601 03 Specifications subject to change without notice FLAME SENSOR BELOW BURNER FLAME ROLLOUT SWITCH BRACKET IGNITER IGNITER BURNER SUPT ASSY BURNER ASSY A11403 Figure 14 Burner Assembly...

Page 23: ...y If the burner flame is proven the blower motor is energized on HEAT speed 25 sec after the gas valve GV is energized Simultaneously the electronic air cleaner terminal EAC 1 is energized and remains...

Page 24: ...flash the status code of the previous fault or status code 11 1 short and 1 long flash if there was no previous fault After the control repeats the code 4 times the control will go through a brief com...

Page 25: ...control will repeat the ignition sequence 3 more times before lockout 14 occurs If flame signal is lost during the blower on delay period blower will come on for the selected blower off delay Check t...

Page 26: ...26 440 04 6601 03 Specifications subject to change without notice 339236 2 Rev A Figure 16 Wiring Diagram...

Page 27: ...r motor capacitor when used Inducer motor module when used Pressure switch es FIRE EXPLOSION ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD Failure to follow this warning could result in danger...

Page 28: ...URE 060 60 000 BTU hr 080 80 000 BTU hr 100 100 000 BTU hr 120 120 000 BTU hr INPUT HEAT 14 14 3 16 17 17 1 2 21 21 24 24 1 2 CABINET WIDTH 16 1600 CFM max 20 2000 CFM max 22 2200 CFM max COOLING AIRF...

Reviews: