background image

MODEL: T7401B

SEVEN-DAY DIAL TIME SWITCH

4 POLE SINGLE THROW

MINIMUM “ON” TIME 3-1/2 HR. UP TO 3-1/2 DAILY ON-OFF OPERATIONS

CONTACT RATINGS:

40 AMP. RESISTIVE EACH POLE 120V- 480V AC.

40 AMP. INDUCTIVE, TUNGSTEN EACH POLE 120V, 208V, 240V, OR

277V AC.  1000 VA PILOT DUTY EACH POLE 120V - 277V AC.

24 FLA,  144 LRA (2 HP) - 120V AC.;  28 FLA,  168 LRA (5 HP) - 240V AC.

SINGLE PHASE

28 FLA, 168 LRA (7 1/2 HP) -208V AC.,  (10 HP) -240V AC. 3 PHASE

CLOCK MOTOR: 125 VOLTS - 60 HZ.

FOR REPLACEMENT MOTOR, ORDER WG1600 

WIRING INSTRUCTIONS
This Time Switch can be wired to control one to four circuits simultaneously on a seven
day schedule. Clock motor voltage may be other than load voltage, but  must be as 
specified. For terminal markings, internal wiring and contact arrangements refer to wiring dia-
gram above.  Use solid or stranded COPPER 

only  wire with insulation to suit installation.

See table for gauge selection. To make power connections remove 1/2 inch of insulation from
wire ends. Insert bare ends of wire under the pressure plate of terminals. Use 3/16 or larger
screw driver to tighten terminal screws firmly. 

REPLACE FRONT INSULATOR BEFORE

TURNING ON ELECTRICITY.

PROGRAMMING INSTRUCTIONS
1.

TO  SET “ON” TIMES, place bright ON trippers against edge of CLOCK-DIAL at
day-of-week and time-of-day when 

“ON” operations are desired. Tighten tripper

screws securely.

2.

TO SET “OFF” TIMES, place dark OFF trippers against edge of CLOCK-DIAL at
times when 

“OFF” operations are desired. Tighten tripper screws securely.

3.

TO SKIP DAYS, omit trippers for the day(s)  automatic operations is/are not required.

4.

TO SET DIAL TO TIME-OF-DAY, turn dial CLOCKWISE and align the exact day-of-
week and time-of-day (AM or PM) on dial with the 

TIME POINTER. Some allowance

may be required to compensate for gear backlash.
CAUTION: DO NOT MOVE POINTER OR FORCE DIAL COUNTERCLOCKWISE.

OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY
: Move MANUAL LEVER below CLOCK-DIAL

left or right as indicated by arrows. This will not affect next automatic operation.

• IN CASE OF POWER FAILURE OR TO ADVANCE/RETARD TIME: Reset time-of-

day, see step 4 of programming instructions.
DISCONNECT ELECTRICITY BEFORE ANY BEHIND-THE-INSULATOR WORK.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS10978

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14
12
10

8

15
20
30
40

60
60
60
75

1/2

1
2

-

2

2 1/2

3
5

120 V
60 HZ

TO
LOADS

SUPPLY

WIRING DIAGRAM

GROUND
SCREW

3
4
5

7 1/2

3
5

7 1/2

10

CLOCK

MOTOR

2

1

A

3

4

5 6

7

8

B

LR3730

158TS10978  8/6/04  10:37 AM  Page 1

Reviews: