MODEL: T21004R

IN RAINPROOF (TYPE 3R) ENCLOSURE FOR INDOOR/OUTDOOR USE 
60 AMP 120/240 VOLT OR 120/208 VOLT SINGLE PHASE, (THREE WIRE) AC

The short circuit rating of this panel is 10000 symmetrical amperes.

IMPORTANT: 

This control panel must be installed according to the National Electrical Code (including article 

680) or Canadian Electrical Code (including section 68) and local code requirements.  This installation is subject to the approval

by the local inspection authority. The main lugs and neutral main are suitable for No. 14 to 2 AWG COPPER conductors. Use

No. 14 to 6 AWG COPPER conductors for branch circuit wiring. Follow gauge selection table and corresponding terminal screw

tightening torque requirements below. Install interchangeable circuit breakers with an interrupting current rating of 10000 

symmetrical amperes, or higher. All circuit breakers in this control panel shall be of the same manufacturer and type. See list of

suitable types below. Follow manufacturers instructions for installing and testing of ground fault circuit breakers (GFCB) and

interrupters (GFCI). Install only LISTED receptacle(s) and/or wiring device(s) inside the enclosure. A LISTED wiring device may

be installed in the rectangular side knockout provided. When panel is outdoors, a LISTED rainproof cover must be installed over

the wiring device in the side knockouts. If this enclosure is used for direct conduit connection to a wet-niche or no niche 

luminaire, one of the connection kits listed below in Note 5 must be used. This control should not be connected to any 

equipment which would cause bodily injury or property damage should it be activated unexpectedly. After wiring, install front

panel over wiring compartment and close unused breaker openings with filler plates. 

KEEP DOOR CLOSED AT ALL TIMES.

CLASS CTL DISTRIBUTION /CONTROL 
PANEL WITH TIME SWITCH

LR3730

UL 508
UL1563

NOTES: 

1. Any Intermatic T100M or ET100CM series Time Switch, PF1000M 

Series freeze protection or RC2000M Series air switch mechanism

may be installed in the bracket provided or in the event an existing 

mechanism is replaced.

2. If this control panel requires bonding, attach a LISTED bonding

terminal of a suitable size using the mounting hole(s) provided on the 

bottom of the enclosure (156T11047A may be ordered).

3. When a back-fed breaker is used in this control panel, order 

22T904A to comply with NEC article 384-16 (g).

4. Wiring devices may be installed in this control panel (order 21T156A

(4) Standoffs for mounting).

5. The following kits are available to connect under water luminaires to this 

enclosure:

1/2” non-metallic - order 156PA13713A

3/4” non-metallic - order 156PA13714A

1” non-metallic - order 156PA13715A

1/2” metallic - order 156PA14336A

TIME SWITCH RATINGS: 

30 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR 1000 VA PILOT DUTY -

120/208/240 VOLT A.C. 2 HP (24 FLA)-120 VOLT A.C., 

5 HP (28 FLA)-240 VOLT A.C.

CLOCK MOTOR: 208-277 VOLTS 60 HZ.

(To order clock motor replacement, specify part no. WG--on motor cover)                   

TIME SWITCH OPERATING INSTRUCTIONS

1. TO SET "ON" AND "OFF" TIMES:

Hold TRIPPERS against edge of CLOCK-DIAL,  pointing to time (AM or PM)

when ON and OFF operations are desired. Tighten tripper  screws firmly.

2. TO SET TIME-OF-DAY:

Pull CLOCK-DIAL outward. Turn in either direction

and align the exact time-of-day on the CLOCK-DIAL

(the time now, when switch is being put into opera-

tion) to the pointer.

-DO NOT MOVE POINTER-

• TO OPERATE SWITCH MANUALLY: Move MAN-

UAL-LEVER below left or right as indicated by

arrows. This will not affect the next operation.

• FOR MORE THAN ONE DAILY ON-OFF OPER-

ATION: Place additional tripper pairs on CLOCK-DIAL (order 156T1978A). 

• IN CASE OF POWER FAILURE: Reset CLOCK-DIAL to proper time of day.

See step 2 above.

ON

TRIPPER

TIME

POINTER

TIME

DIAL

OFF

TRIPPER

MANUAL

LEVER

IIN

NT

TE

ER

RM

MA

AT

TIIC

C IIN

NC

CO

OR

RP

PO

OR

RA

AT

TE

ED

D

SPRING GROVE ILLINOIS 60081-9698

158TP12178  

SUITABLE FOR SWIMMING POOL / SPA APPLICATIONS AND FOR DIRECT CONDUIT CONNECTION TO A WET-NICHE OR NO NICHE LUMINAIRE.

*

TORQUE CIRCUIT BREAKER LUGS TO VALUES SPECIFIED ON 

CIRCUIT BREAKERS

WIRING INFORMATION - COPPER CONDUCTORS ONLY

TERMINAL TORQUE*

GENERAL

GENERAL

PURPOSE

MAX MOTOR

PURPOSE

BRANCH

SUPPLY

LINE AND

LOAD

BRANCH

CIRCUIT

WIRE SIZE

CIRCUIT

NEUTRAL NEUTRAL (CONTINUOUS

CIRCUIT

MAXIMUM

75˚C MIN

BREAKER

MAIN

AND

DUTY)

BREAKER

CURRENT

INSULATION

RATING

LUGS

GROUND 120V.     240V.

RATING

CAPACITY

AWG

AMP

LB-IN

LB-IN

HP        HP

AMP

AMP

14

15

35

20

1/2         1

15

12

12

20

35

20

1            2

20

16

10

30

35

20

1 1/2    3

30

24

8

50

40

25

2          5

40

32

6

60

45

35

---         ---

60

44

SUITABLE  LISTED BREAKERS

CIRCUIT BREAKER

FILLER

MANUFACTURER

SINGLE DOUBLE TWIN QUAD

GFCB

PLATE

CUTLER-HAMMER

BR

BR

BRD

BRD

GFCB

BRFP

MURRY

MP-T

MP-T

MH-T MH-T

MP-GT   LX100FP

SIEMENS

QP

QP

QT

QT

QPF

QF3

SQUARE D

HOM

HOM

HOMT HOMT

----

HOMFP

THOMAS & BETTS

TB

TB

TBBD TBBQ

GFB      FP-1C-TB