LR3730

MODEL: T175CR

24 HR DIAL TIME SWITCH WITH “SKIPPER

®

AND SPRING-WOUND CARRY-OVER MOTOR

ONE NO - ONE NC CONTACTS 

MAY BE WIRED AS SINGLE POLE DOUBLE THROW

IN TYPE 3R RAINPROOF ENCLOSURE
40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR
1000 VA. PILOT DUTY PER POLE - 120/208/277 VOLT AC;
2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.

WIRING INSTRUCTIONS: To wire switch follow diagram above. Use solid
or stranded COPPER 

only wire with insulation to suit installation. See gauge

selection table for normal service applications. To make power connections
remove 1/2 inch of insulation from wire ends. Insert bare ends of wire under
the pressure plate of terminals. Use 3/16 or larger screwdriver to tighten termi-
nal screws firmly. (25 lb-in minimum). 

REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY

PROGRAMMING INSTRUCTIONS
1.

TO SET “ON” AND “OFF” TIMES: Hold trippers against edge of

CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional
tripper pairs on 

CLOCK-DIAL order 156T1978A.

2.

TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either
direction and align the exact time-of-day on the 

CLOCK-DIAL (the 

time now, when switch is being put into operation) to the pointer.

DO NOT MOVE POINTER.

3.

TO SKIP OPERATION(S) ON SELECTED DAY(S): Insert SKIPPING

SCREW(S) in SKIPPER WHEEL for day(s) automatic operation(s)
is/are NOT required. Tighten screws firmly. Move

MANUAL LEVER to

“OFF” and rotate SKIPPER WHEEL to locate correct day-of-week
opposite

DAY ARROW--”YESTERDAY” if ON/CUTOUT TRIPPER

has not yet advanced wheel 

“TODAY” if it has.

OPERATING INSTRUCTIONS

TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below

CLOCK-DIAL left or right as indicated by arrows. This will not effect
next operation.

CAUTION: TO AVOID SLOW SWITCH ACTION FAILURE, DO NOT OPERATE
SWITCH MANUALLY NOR PLACE A TRIPPER 4 HOURS PRIOR TO
ON/CUTOUT TRIPPER SWITCHING.

IN CASE OF POWER FAILURE, reset  CLOCK-DIAL to
proper  time-of-day. See programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS10932

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE
INSULATION CLEARS

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

SINGLE PHASE

3 PHASE

14
12
10

15
20
30

60
60
60

1/2

1
2

2

2 1/2

3
5

N/A

N/A

TIME

TIME

OFF

MANUAL

ON/CUTOUT

DAY

SKIPPER

SKIPPING

CLOCK MOTOR: 110-125 VOLTS - 60 HZ.

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO

CLOCK

A

1

2

3

4

N

120V

TO

LOAD

GRD

LINE 

TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES

WIRING DIAGRAM

Project1  7/27/04  4:35 PM  Page 1