MODEL: T105

24 HOUR DIAL TIME SWITCH 

ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS

MAY BE WIRED AS SINGLE POLE DOUBLE THROW

40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN OR
1000 VA. PILOT DUTY PER POLE - 120/208/240VOLT AC;
2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC.

WIRING INSTRUCTIONS: To wire switch follow diagram above.
To wire as 

SINGLE POLE NORMALLY CLOSED, move clock

motor lead from terminal 

to 1, and connect LINE to 1, LOAD to

2. To wire as SINGLE POLE DOUBLE THROW, install jumper
(the same gauge as 

Line wire) between and and connect

LINE to 2, LOADS to and 4. NEUTRAL connection always as
shown. Use COPPER wire only. For gauge selection and wire
connection, see details below. Use 3/16 or larger screwdriver,
tighten terminal screws firmly (25lb-in minimum). 
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY

PROGRAMMING INSTRUCTIONS
1.

TO SET “ON” AND “OFF” TIMES: Hold trippers against edge 
of 

CLOCK-DIAL, pointing to time (AM or PM) when ON and

OFF operations are desired, tighten tripper screws firmly. For
additional tripper pairs on 

CLOCK-DIAL order 156T1978A.

2.

TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in
either direction and align the exact time-of-day on the 

CLOCK-

DIAL (the time now, when switch is being put into operation) to
the pointer. 

DO NOT MOVE POINTER.

OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: 
Move MANUAL LEVER 

below 

CLOCK-DIAL left or right as indicated by arrows. This 

will not effect next operation.

• IN CASE OF POWER FAILURE, reset  CLOCK-DIAL to

proper  time-of-day. See programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS11760

TIME

POINTER

TIME
DIAL

OFF
TRIPPER

MANUAL
LEVER

ON
TRIPPER

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14
12
10

8

15
20
30
40

60
60
60
75

1/2

1
2

-

2

2 1/2

3
5

N/A

N/A

CLOCK MOTOR: 110-125 VOLTS - 60 HZ.

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.

LR3730

WIRING
DIAGRAM

TYPICAL WIRING: SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES

GROUND

120V

SUPPLY

CLOCK

MOTOR

GRD.

N

LINE

TO
LOAD

A

1

2

3

4