Intermatic T10404R Manual Download Page 1

TIME SWITCH OPERATING INSTRUCTIONS

1. TO SET “ON” AND “OFF” TIMES: Hold  TRIPPERS 

against edge of CLOCK-DIAL, point-

ing    to  time  (AM  or  PM)  when  ON 

and  OFF  operations  are  desired.

Tighten  tripper  screws  firmly.

2. TO  SET  TIME-OF-DAY:  Pull 

CLOCK-DIAL  outward.  Turn  in 

either  direction  and  align  the  exact 

time-of-day  on  the  CLOCK-DIAL  (the  time  now,  when 

switch is being put into operation) to the 

POINTER.

DO NOT MOVE POINTER

•  TO  OPERATE  SWITCH  MANUALLY:  Move 

MANUAL  LEVER  below  CLOCK-DIAL  left  or  right  as 

indicated  by  arrows,  This  will  not  affect  next 

operation.

•  FOR MORE THAN ONE DAILY ON-OFF 

OPERATION: Place additional tripper pairs on CLOCK-

DIAL (order 156T1978A).

•  IN CASE OF POWER FAILURE, reset CLOCK-DIAL 

to proper time-of-day. See step 2 above.

  

 

 INTERMATIC INCORPORATED

    SPRING GROVE, ILLINOIS 60081-9698

158TP10864                                                                                                               

CLOCK

DIAL

TIME

POINTER

OFF

TRIPPER

MANUAL

LEVER

ON

TRIPPER

TIME SWITCH RATINGS:

DOUBLE POLE SINGLE THROW (DPST)

30 AMP, RESISTIVE, INDUCTIVE, TUNGSTEN

OR 1000 VA PILOT DUTY - 120/208/240 VAC

2 HP (24 FLA)-120 VAC, 5 HP (28 FLA)-240 VAC

CLOCK MOTOR:208/277 VOLTS - 60 HZ.

(TO ORDER CLOCK MOTOR REPLACEMENT,SPECIFY PART NO. 

WG--ON MOTOR COVER)

MODEL:

 

T10404R

IN RAINPROOF (TYPE 3R) ENCLOSURE FOR INDOOR OUTDOOR USE 

SUITABLE FOR SWIMMING POOL / SPA APPLICATIONS AND FOR DIRECT CONNECTION OF UNDERWATER LIGHTS.

92 AMP PER LEG, 168 AMP MAX., 120/240 VOLT OR 120/208 VOLT SINGLE PHASE, (THREE WIRE) AC.

IMPORTANT:

 

This Control Panel  must be installed according to the National Electrical Code (including Article 680) 

or Canadian Electrical Code (including Section 68) and Local Electrical Codes. This installation is subject to the approval

by the local inspection authority. USE COPPER CONDUCTORS ONLY. Do not exceed the maximum ratings of individual 

components, wiring devices, and current carrying capacity of conductors. If heater protection is required, install FIREMAN 

SWITCH kit (156T4042A may be ordered). For grounding of the installation, refer to Article 250 and 680 of the National 

Electrical Code. (For Canadian Installations: Section 10 and 68 of the Canadian Electrical Code). Install only APPROVED

wiring  device(s)  inside  the  enclosure.  An  APPROVED  wiring  device  may  be  installed  in  the  rectangular  side 

knockout  provided.  When  panel  is  outdoors,  an  APPROVED  rainproof  cover  must  be  installed  over  the  wiring 

device in the side knockout. If this enclosure is used for direct connection of underwater lights, refer to 1999 NEC 680-

21(b), 2002 NEC 680-24(b) or CEC 68-060, 062 and 066 for further details. This Control should not be connected to any

equipment which would cause bodily injury or property damage should it be activated unexpectedly. After wiring, install 

front panel over wiring compartment.      

KEEP DOOR CLOSED AT ALL TIMES

.

NOTES:

 

1.  Any Intermatic T100M or ET100CM series Time Switch, P1353ME 

 

3 Circuit Control, PF1000M Series Freeze Protection or RC2000M Series 

 

Air Switch Mechanism may be installed in the bracket provided or in the 

 

event an existing mechanism is replaced.

2.  If this control panel requires bonding, attach an APPROVED bonding 

 

terminal of a suitable size using the mounting hole(s) provided on the 

 

bottom of the enclosure (156T11047A may be ordered).

3.  Wiring devices may be installed in this control panel (order

 

21T156A (4) Standoffs for mounting).

CONTROL PANEL WITH 

TWO TIME SWITCHES

LR3730

UL508

UL1563

NEC680

WIRING DIAGRAM AND INSTRUCTIONS FOR INTERCONNECTING TIME 

SWITCHES WHEN USED AS SWIMMING POOL EQUIPMENT CONTROL

1.  Disconnect  the  clock  motor  leads  of  the  CLEANER  CONTROL  TIMER.

2.  Connect  240  volt  supply  and  the  clock  motor  leads  of  the  CLEANER

   CONTROL  TIMER  to  terminals  #1  and  #3  of  the  FILTER  TIMER.

3.  Connect terminals #2 and #4 of Filter Timer to terminals #1 and #3 of the

  Cleaner Control Timer (using short jumpers).

4.  Connect  240  volt  load  of  cleaner  pump  to  terminals  #2  and  #4  of 

  CLEANER CONTROL TIMER.

CLOCK

MOTOR

CLOCK

MOTOR

SUPPLY 

TO FILTER

PUMP

TO POOL

CLEANER

FILTER TIMER 

CLEANER CONTROL TIMER

WIRING INFORMATION - COPPER CONDUCTORS ONLY

 

 

 

 

 

  

GENERAL

 

 

 

 

 GENERAL   PURPOSE

 

 

 

 

PURPOSE    BRANCH

 

 

 

 

 BRANCH    CIRCUIT

 WIRE SIZE   

 

 

 CIRCUIT  MAXIMUM

  75˚C MIN  TERMINAL   

 

BREAKER   CURRENT

INSULATION    TORQUE     120V.  240V.   RATING 

 CAPACITY

     AWG 

   LB-IN 

 HP    HP      AMP 

    AMP

      14 

     20 

 1/2     1       15 

     12

      12 

     20 

  1 

   2       20 

     16

      10 

     20 

1 1/2     3       30 

     24

       8 

     25 

  2 

   5       40 

     32

 

 MAX MOTOR

      LOAD

(CONTINUOUS

      DUTY)