background image

MODEL: T101

24 HOUR DIAL TIME SWITCH 

SINGLE POLE SINGLE THROW (SPST)

40 AMP. RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VOLT AC;
2 HP (24 FLA) - 120V AC; 5 HP (28 FLA) - 240V AC

WIRING INSTRUCTIONS: To wire switch follow diagram above.
Use solid or stranded COPPER only wire with insulation to suit
installation. See gauge selection table for normal service applica-
tions.To make power connections remove 1/2 inch of insulation
from wire ends. Insert bare ends of wire under the pressure plate
of terminals. Use 3/16 or larger screwdriver to tighten terminal
screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY

PROGRAMMING INSTRUCTIONS
1. TO SET “ON” AND “OFF” TIMES: Hold trippers against edge 

of  CLOCK-DIAL, pointing to time (AM or PM) when ON and
OFF operations are desired, tighten tripper screws firmly. For
additional tripper pairs on CLOCK-DIAL order 156T1978A.

2. TO  SET TIME-OF-DAY: Pull  CLOCK-DIAL outward. Turn in

either direction and align the exact time-of-day on the CLOCK-
DIAL 
(the time now, when switch is being put into operation) to
the pointer. DO NOT MOVE POINTER.

OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: 
Move MANUAL LEVER 

below CLOCK-DIAL left or right as indicated by arrows. This 
will not effect next operation.

• IN CASE OF POWER FAILURE, reset  CLOCK-DIAL to

proper  time-of-day. See programming instructions.

INTERMATIC INCORPORATED

SPRING GROVE, ILLINOIS 60081-9698

158TS10941

TIME

POINTER

TIME
DIAL

OFF
TRIPPER

MANUAL
LEVER

ON
TRIPPER

CLOCK

MOTOR

GROUND

A

1

2

GRD.

120V

SUPPLY

TO

LOAD

LINE 

NEUT.

WIRING

DIAGRAM

PRESSURE PLATE

TERMINAL SCREW

MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE

MINIMUM

COPPER

WIRE SIZE

(AWG)

MAX.

LOAD

(AMP)

MIN.

INSUL-

ATION

TEMP(°C)

75°C INSULATION MAX. MOTOR

LOAD (HP)

SINGLE PHASE

3 PHASE

120 V.

240 V.

208 V.

240 V.

14
12
10

8

15
20
30
40

60
60
60
75

1/2

1
2

-

2

2 1/2

3
5

N/A

N/A

CLOCK MOTOR: 110 -125 VOLTS - 60 HZ.

CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.

LR3730