background image

Main Breaker

2-Pole, 20 A circuit

breaker shown

A=Black (Line)
B=Black (Line)
C=Neutral (White)

Panel Installation

120 VAC Two wire single phase with 

separate ground.

Found at connections for individual 

pieces of equipment such as pumps, 

single phase motors and HVAC applications. 

NOTE:

 Both Black wires connect to Line.  

Line

Neutral

Ground

0 V

120 V

120 V

Neutral/

   Grounded 

  (WHITE)

   Line

(BLACK)

   Line

(BLACK)

Service

Transformer Secondary

Service Equipment Overcurrent device

L1 (black)

L2 (black)

Neutral (white)

120/240 VAC 

PS3000

Type 1 installation:

A typical installation of a type 1 SPD will be connected between the secondary of 
the service transformer and the line side of the service panel. This installation is 
intended to be installed without overcurrent protection to the SPD.

1. Determining location:

•  Ensure conductor lengths are as short and straight as possible for

best performance. Do not coil excess wire. The SPD functions best if
all bends in wires are rounded, ideally to a 4” radius. Hard 90 degree
bend will reduce efficiency. Cut all leads to the correct length. Do not coil
excess leads.

•  Install appropriate weatherproof fittings if the unit is to be mounted

outside.

2.  

Ensure all mounting and connections are correct and secure. Once
energized the green indicator LED will be ON and visible through the cover
of the SPD.

Type 2 installation:

A typical installation of a type 2 SPD will be connected to the load side of the 
service panel and is intended to be installed with overcurrent protection to the 
SPD.

1. Determining location:

•  Ensure conductor lengths are as short and straight as possible for

best performance. Do not coil excess wire. The SPD functions best if
all bends in wires are rounded, ideally to a 4” radius. Hard 90 degree
bend will reduce efficiency. Cut all leads to the correct length. Do not coil
excess leads.

•  Install appropriate weatherproof fittings if the unit is to be mounted

outside.

2.  Connect the white wire from the SPD to the neutral bus bar in the panel as

shown.
•  Connection may also be made to the neutral/ground bus bar if panel

does not have a separate ground bus bar.

3.  Connect the two black wires to a circuit breaker as shown. For best

performance from SPD the maximum recommended circuit breaker size of
240 VAC, 20 A, 2-pole should be used.

4.  Ensure all mounting and electrical connections are correct and securely

fastened. Once energized the green indicator LED will be ON and visible
through the cover of the SPD.

Maintenance:

AC Voltage SPD:
•  

Periodically check SPD to ensure green indicator LED is ON. If green
LED is OFF, protection has diminished and the SPD should be replaced
immediately.

INSTALLATION INSTRUCTIONS

IMPORTANT SAFETY INSTRUCTIONS • SAVE THESE INSTRUCTIONS

Model PS3000

Type 1 or Type 2 Surge Protection Device (SPD)

• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Intended for indoor or outdoor use.
• Installation and/or wiring must be in accordance with national and local electrical code and/or Canadian Electrical Code requirements.
• Installation and service to be performed by a qualified licensed technician or electrician.
• Suitable for use on a circuit capable of delivering not more than 20,000 rms symmetrical amperes.
• This unit contains no serviceable parts.

    

WARNING

Risk of Fire or Electric Shock

NOTICE

• 

Thoroughly read instructions before installing SPD Unit.

• 

This product does not protect against lightning strikes.

• L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité local en vigueur et/ou du Code canadien de l’électricité.
• L’installation et l’entretien doivent être effectués par un technicien ou électricien qualifié.
• Convient à un circuit capable de fournir PAS plus de 20 000 A efficaces symétriques.
• Cet appareil ne contient aucune pièce réparable.

    

AVERTISSEMENT

Risque d’incendie ou de choc électrique

http://waterheatertimer.org/How-to-wire-Whole-house-surge-protector.html