background image

Electronic 7-Day 

Time Switch

Installation and User Instructions

MODEL ET1700 Series

With Battery  

Carryover

Front View

Rear View

B

A

Time Switch

• Input Voltage: 120/208/240/277 VAC, 60 Hz
• Power Consumption: 6.0 W Max.
• Contact Configuration: SPST (ET1705C), DPST (ET1725C), and

SPDT (ET1715C). See wiring diagrams on next page.

Switch Ratings—ET1705C, ET1725C (per pole)

• 30 A Inductive/Resistive, 120/240 VAC, 60 Hz
• 20 A Ballast, 120-277 VAC, 60 Hz
• 20 A Resistive, 28 VDC
• 5 A Tungsten: 120/240 VAC, 60 Hz
• 1 HP, 120 VAC, 60 Hz
• 2 HP, 240 VAC, 60 Hz

Switch Ratings—ET1715C (NO/NC) Normally Open/Normally Closed Contact 

• 20 A/10 A Inductive/Resistive, 120/240 VAC, 60 Hz
• 20 A/3 A Ballast, 120-277 VAC, 60 Hz
• 5 A Tungsten: 120/240 VAC, 60 Hz
• 1 HP / ¼ HP, 120 VAC, 60 Hz
• 2 HP / ½ HP, 240 VAC, 60 Hz

Set Points (Events)

—Each load output of the Time Switch can support

up to 14 timed ON and 14 timed OFF events per day.

Battery-Powered Clock Operation

—3 years minimum (uses 2 AAA indus-

trial grade alkaline batteries, supplied)

Minimum ON or OFF time

—1 minute

Maximum ON or OFF time

—6 days, 23 hours, 59 minutes

Shipping Weight

—2.5 lb. (1.1 kg)

The Intermatic ET1700 Series Electronic 7-Day Time Switch 
automatically switches loads to a preset weekly schedule with to-the-
minute accuracy. 
The independent 7-day programming provides complete flexibility for 
applications where load switching differs each day of the week. 
Use the ET1700 series as an ON/OFF timer in applications requiring 
7-day load control such as lighting, air conditioning systems, pumps,
etc. Each load output of the Time Switch can support up to 14 timed
ON and 14 timed OFF events per day. The program can be overridden
by pushing the ON/OFF load override button(s).
The ET1700 Series Time Switch is designed to directly switch tungsten 
or ballast loads up to its rating, and inductive or resistive loads up to 
30A at 120, 208, 240, or 277 VAC.

Specifications

Description

    

WARNING

Risk of Fire or Electric Shock

• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
•  Installation and/or wiring must be in accordance with national and local electrical code

requirements.

 

 For outdoor locations or wet locations (rain-tight), conduit hubs that comply with requirements of
the UL514B (standard for fitting conduit and outlet boxes) are to be used.

•  This enclosure does not provide grounding between conduit connections. When metallic conduit

is used, you must also install grounding type bushings and jumper wire.

•  For plastic enclosures, bonding between conduit connections is not automatic and must be

provided as part of the installation.

• Use #18 - #10 AWG wires, rated at least 75°C - COPPER conductors ONLY.
•  If the power disconnect point is out of sight, lock it in the OFF position and tag it to prevent

unexpected application power.

•  Make sure there is no wire insulation under the terminal plate on the time switch connector.

Firmly tighten terminal screws.

• Do not remove insulator that is covering terminals.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.

NOTICE

•  Do NOT touch circuit board components, contact can create a static discharge, which can

damage the microprocessor.

Enclosures

—Three enclosure options are available. 

• ET17x5C – TYPE 1 indoor metal enclosure
• ET17x5CR – TYPE 3R indoor/outdoor lockable metal enclosure
• ET17x5CPD82 – TYPE 3R indoor/outdoor lockable impact resistant 

polycarbonate enclosure with clear cover

Knockouts

—Combination 1/2-3/4 inch size, 1 on back and each side, 

2 on bottom

Wire Size

—AWG #18 through #10

Slide down

to remove 

battery case

Snap out catch

Tilt top forward

Installation Instructions

3.  The timer is shipped with DST (Daylight Saving

Time) enabled. To disable DST, insert a jumper
at location marked DST. See location 

B

 in Rear

View above and detail at the right.

4.

   ET1725C  ONLY—

Decide whether you want

to control multiple loads simultaneously (SIM),
independently (IND), or with a 2-second pulse
(PUL) (e.g., for use with mechanically held
contactors or bell ringing applications), and
make sure the jumper is positioned accordingly. 
See location 

B

 in Rear View above and detail

at the right. (The unit is shipped with the loads
set for IND.)

2.  Set voltage selector for desired input voltage.

The timer is shipped with voltage set for 120
VAC. To operate at 208, 240 or 277 VAC, move
the selector switch to the desired setting as
marked on the circuit board. See location 

A

 in

Rear View above and detail at the right.

1.  Remove the mechanism 

from the case by

depressing the catch at

the top of the case and

pulling out, as shown.

Reviews: