Operation Manual
Emergency Combination System
ECS-9216
Page 1: ...Operation Manual Emergency Combination System ECS 9216 ...
Page 2: ...ment 2 Important Safety Instructions 2 Features 3 Operation 3 Front Panel 4 Rear Panel 5 Installation 7 Applications 9 Block Diagram 11 Specifications 12 Service Procedures 13 Schematic 13 Parts List 13 Variations and Options 13 Warranty 13 EMERGENCY COMBINATION SYSTEM ...
Page 3: ...illed with liquids such vases shall be placed on the apparatus Worded WARNING FOR YOUR PROTECTION PLEASE READ THE FOLLOWING WATER AND MOISTURE Unit should not be used near water e g near a bathtub washbowl kitchen sink laundry tub in a wet basement or near a swimming pool etc Care should be taken so than objects do not fall and liquids are not spilled into the enclosure through openings This symbo...
Page 4: ...ectrician for replacement of the obsolete outlet 10 Protect the power cord from being walked on or pinched particularly at plugs convenience receptacles and the point where they exit from the apparatus 11 Only use attachments accessories specified by the manufacturer 12 Use only with the cart stand tripod bracket or table specified by the manufacturer or sold with the apparatus When a cart is used...
Page 5: ... 9216 Operation Operation 1 Supply the power 2 The fire alarm will be given automatically if the fire sensor signal is detected 3 Select the speak channel after selecting on Emergency or Normal On Normal mode the speaker channel led is displayed on green On Emergency mode the speaker channel led is displayed on red 4 The all switch is for selecting all 16 speaker channels 5 The priority is EMERGEN...
Page 6: ...d is green 3 PRIORITY STATUS DISPLAY LEDS These leds display the priority status The priority is Emergency Timer Remote1 Remote2 Main BGM 4 SPEAKER CHANNEL SELECT SWITCHS AND SPEAKER CHANNEL LEDS These switch select individual channel 1 through 16 On the Emergency mode the speaker channel leds are red On the Normal mode the speaker channel leds are green ALL ZONE 1 ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE...
Page 7: ...e Inter M Power Distributor ex PD 9359 This is connected to the remote control switch of Power Distributor 7 TIMER SWITCH TERMINAL This terminal is for input of the Inter M Timer ex PW 9242N This is connected to the timer switch of Inter M Timer All speaker channels will be selected when the timer switch is on 8 LINK IN CONNECTOR This connector is for extension of additional ECS 9216 This is conne...
Page 8: ...UTPUT CONNECTOR This connector is the DC power input and output connector The DC input is for the connection of 24VDC power supply The DC output is for the connection of 24VDC power supply to an additional unit in the system 11 SPEAKER OUTPUT TERMINAL This terminal is for the speaker line output 12 AMP INPUT TERMINAL This terminal is for connecting to the speaker output of the amplifier ...
Page 9: ...M RM 916 Figure 1 4 Connect the emergency panel connector to the Inter M EP 9216 Figure 2 5 Connect the fire sensor input connector to the fire panel Each 16 fire sensor input channels have 3 ports Figure 3 4 6 Connect the power distributor terminal to the remote control switch of Inter M Power Distributor 7 Connect the timer switch terminal to the remote out of Inter M Timer ex PW 9242N 8 Connect...
Page 10: ...ent fire sensor signal should be connected to the another pin in this case pin No4 and 5 on the same fire sensor input channel Internally the 3 pins of same fire sensor input channel are separated by diodes Fire sensor input connector pin NO and function Figure 3 Connection of the fire sensor input connector Figure 4 CH6 CH7 CH8 CH5 CH3 CH2 CH1 CH4 CH1 8 1 2 3 4 8 7 6 5 9 10 11 12 14 13 18 19 20 2...
Page 11: ... 6 ZONE 7 ZONE 8 ES PS ZONE 9 ZONE 10 ZONE 11 ZONE 12 EMERGENCY TIMER REMOTE 1 REMOTE 2 MAIN ZONE 13 ZONE 14 ZONE 15 ZONE 16 OFF ON OUTPUT STAND BY MIC MIC VOLUME MAX MIN FIRE 10dB CLIP 40dB PROT OUTPUT PROTECTION POWER OFF ON PHONES PW 9242N EP 9216 ECS 9216 Audio Line Fire Panel Control Line PC 9335A PA 9336 ...
Page 12: ...EMERGENCY COMBINATION SYSTEM 10 ECS 9216 PW 9242N EP 9216 Fier Panel ECS 9216 SPEAKER PC 9335A PA 9336 PD 9359 Audio Line Control Power Line PB 9207A AC IN ...
Page 13: ... ECS 9216 Block Diagram Block Diagram RM1 RM2 INPUT FIRE SENSOR INPUT CH1 16 AMP INPUT CH1 16 FRONT SWITCH LED INTERFACE CPU NOR EM RELAY CH1 16 EMERGENCY PANEL INTERFACE RS 422 INTERFACE PD OUTPUT TIMER IN INTERFACE AMP OUPUT CH1 16 ...
Page 14: ... Main Link in out Interface RS 422 19200bps Data 8bits Stop 1bit Non Parity bit Start 1bit Link in out Interface Distance 1 2km Operating Temperature 0 C 40 C Power Source 24VDC Power Consumption 14W Weight 5kg 11 0lb Dimensions 482 W x88 H x280 D mm 19 W x3 5 H x11 D in Specifications and design subject to change without notice ...
Page 15: ...vailable by contacting your warranty provider Variations and Options Variations and Options Variations Products supplied through legitimate sources are compatible with local AC power requirements Options No optional items are available for this product Warranty Warranty Warranty terms and conditions vary by country and may not be the same for all products Terms and conditions of warranty for a giv...
Page 16: ... but rather a global company that is truly international in scope with factories and offices in Korea and China and sales and marketing operations located in Japan Europe and the U S A With more than 850 employees around the globe Inter M is well poised for further growth and expansion INTER M AMERICAS INC 1 EAST BEACON LIGHT LANE CHESTER PA USA 19013 4409 TEL 1 610 874 8870 FAX 1 610 874 8890 Hom...