2.
INSTALLATION
https://intellimeter.ca/pages/downloads#videos
Intellimeter i-meter®45 Installation
&Troubleshooting
to get detailed information about the installation process.
WARNING:
Verify the number of breakers is the same as the number of meters assigned for that panel board.
Follow the installation drawings. Group the assigned modules to the identified panel board.
Referring to the diagram below, CTs can be embedded in the distribution panel. If the customer
has supplied a special compartment for the meter with their electrical panel, Intellimeter will
install the meter and have the SPE-1000 field evaluation completed. Otherwise, the meter will be
installed in an external enclosure to be mounted near the electrical panel for ease of servicing.
Install the modules into their appropriate position.
Install the voltage connectors to the meter modules and dress the wires so they are protected
from damage during feeder and branch circuit installation.
Terminate the voltage reference chain to the designated, 15Amp breaker and ensure the proper
phasing retained as per drawings.
Install the communication connectors to the meter modules and dress the wires they are
protected from damage during feeder and branch circuit installation.
Communication cable is to be terminated to a junction box outside of the panel board by the
electrical contractor.
2.1.
i-meter®45 Wiring Guide
In the i-meter®45 wiring diagram figure below, the branch CTs connect to Port A, B, C, D using a
ribbon cable.
Port A: CT1 – CT12
Port C: CT13 – CT21
Port B: CT22 – CT33
Port D: CT34 – CT42
CT43, CT44, CT45 are connected directly to the meter module with 2 pin connectors.
Voltage Input: L1, L2, L3 and N
Display- MC required- optional only if non-sealed: i-meter®45 MDU = meter display unit- comes
with a 6 ft. cable for connecting directly to the meter.