I-METER

 

®

 

45 

INSTALLATION AND 

USER MANUAL 

 

Summary of Contents for I-METER 45

Page 1: ...I METER 45 INSTALLATION AND USER MANUAL ...

Page 2: ...er 45 Manual TABLE OF CONTENTS 1 PRODUCT DESCRIPTION 4 1 1 Applications 4 1 2 Specifications 5 2 INSTALLATION 6 2 1 i meter 45 Wiring Guide 6 2 2 i meter 45 CT Rail 7 2 3 i meter 45 CT Interface Board 10 3 I METER 45 MDU DISPLAY 15 4 i meter 45 MODBUS MODULE 15 4 1 Electrical connection 16 4 2 Register Mapping 17 ...

Page 3: ...a return material authorization RMA number should be obtained from ICI STATEMENT OF CALIBRATION The accuracy and calibration of our instruments are traceable to Measurement Canada a division of Industry Canada CONFIGURATION The i meter 45 meter series can only be configured by Intellimeter Canada Inc at ICI s factory according to the customers provided panel schedule INSTALLATION CHECKLIST Make su...

Page 4: ...ent Canada MC and Measurement California and certified by CSA UL i meter 45 meter 1 1 Applications The i meter 45 is designed for a wide variety of applications In Multi Customer Metering systems MCMS applications property managers can use the data for cost allocation and demand side management This meter can be programmed for different service types They are Single phase two wire metering capabil...

Page 5: ...A CTs Self Shorting Protection Instrument Transformers Interface Yes Measurements Total Energy kWh kVAh are accumulated in non volatile memory on the meter Real Time Measurements V I kW kVA kVar pf Hz Per phase V I Total Harmonic Distortion THD Per phase V I individual harmonic order up to 23rd Communication ModBus RTU or TCP IP BACnet MSTP or TCP IP and pulse output Frequency 45 to 65 Hz Accuracy...

Page 6: ... ease of servicing Install the modules into their appropriate position Install the voltage connectors to the meter modules and dress the wires so they are protected from damage during feeder and branch circuit installation Terminate the voltage reference chain to the designated 15Amp breaker and ensure the proper phasing retained as per drawings Install the communication connectors to the meter mo...

Page 7: ...r and other information on the meter All meter modules are assigned within the panel board and are identified with respect to position or section of breakers Follow the installation drawings that are supplied with the units Do not leave the secondary CT open when current is flowing through the primary circuit This refers to instrument CTs as ICI milliamp CTs are self protected Contact ICI if there...

Page 8: ...Page 8 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual ...

Page 9: ...Page 9 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual Typical Application Using CT rail Typical Application Using CT rail ...

Page 10: ...the CT leads do not need to be removed from the meter module If required connect the CT wire connector to the identified terminal on the correct meter module There may be several modules within a panel board confirm the meter number on the CT connector label Install the voltage connectors to the meter modules and dress the wires so they are protected from damage during feeder and branch circuit in...

Page 11: ...Page 11 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual 12 CT rail for 100A CTs 12 CT rail for 200A CTs ...

Page 12: ...Page 12 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual Thei meter 45CTterminalboard ...

Page 13: ...Page 13 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual Current Transformer Interface Module ...

Page 14: ...Page 14 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual Typical Application Using CT Terminal Board ...

Page 15: ...play 4 i meter 45 MODBUS MODULE The i meter 45 ModBus module enables the meter to communicate on a ModBus system It presents real time measurements such as voltage current THD etc The normal mode of the module supports RTU ModBus communication over an RS 485 network Within 30 seconds of power up the module will enter the normal mode of operation that supports ModBus communication By default the mo...

Page 16: ...Page 16 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual 4 1 Electrical connection ...

Page 17: ...te 41003 3 9600 bps 4 19200 bps 5 38400 bps 6 57600 bps 7 115200 bps The Baud Rate takes effect after power cycling Table 5 2 Meter 0 Information Modbus Address Name Format Unit Default 41100 Active Phases Bit map x1 41101 Voltage A UINT32 0 001V 41103 Voltage B UINT32 0 001V 41105 Voltage C UINT32 0 001V 41107 Current A UINT32 0 001A 41109 Current B UINT32 0 001A 41111 Current C UINT32 0 001A 411...

Page 18: ...urrent 41157 Average of the current from each phase 4 Meter 0 is assigned to the main meter if you program the configuration with main meter Table 5 3 Meter x Information Modbus Address Name Format Unit Default 4xx00 Active Phases Bit map x1 4xx01 Voltage A UINT32 0 001V 4xx03 Voltage B UINT32 0 001V 4xx05 Voltage C UINT32 0 001V 4xx07 Current A UINT32 0 001A 4xx09 Current B UINT32 0 001A 4xx11 Cu...

Page 19: ... that this element is associated with 47xxx 1 THD UINT16 0 01 Total harmonic distortion for this waverform 47xxx 2 Fundamental UINT16 0 01 Fundamental component for this waveform 47xxx 3 2nd Harmonic UINT16 0 01 2nd harmonic component for this waveform 47xxx 4 3rd Harmonic UINT16 0 01 3rd harmonic component for this waveform 47xxx 5 4th Harmonic UINT16 0 01 4th harmonic component for this waveform...

Page 20: ...veform 47yyy 6 5th Harmonic UINT16 0 01 5th harmonic component for this waveform 47yyy 7 6th Harmonic UINT16 0 01 6th harmonic component for this waveform 47yyy 8 7th Harmonic UINT16 0 01 7th harmonic component for this waveform 47yyy 9 8th Harmonic UINT16 0 01 8th harmonic component for this waveform 47yyy 10 9th Harmonic UINT16 0 01 9th harmonic component for this waveform 47yyy 11 10th Harmonic...

Page 21: ...Page 21 Intellimeter Canada Inc 1125 Squires Beach Road Pickering ON L1W 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual i meter 45 External Enclosure Model ...

Page 22: ... 3T9 Tel 905 839 9199 Copyright 2019 i meter 45 Manual Thank you for giving us the opportunity to serve you We appreciate your business and the confidence you have placed in us Please visit us https intellimeter ca or call us 905 839 9199 if you need any further assistance ...