RECOMMENDED PERIODICAL MAINTENANCE
The lighting fitting should be tested on regular basis in accordance with valid laws and regulations. The results of
the tests should be recorded and stored for the use of a fire safety inspector.
One time daily
It has to be visually checked if the LED indicator in the lighting fitting lights up green.
One time each month
It is necessary to disconnect the AC power supply for 30 seconds and check whether the lamp is operating in
emergency mode - the green LED indicator turns off, and 12 white LEDs light up.
One time each year
Disconnect the AC power supply and test if the lamp operates in emergency mode for a specified time. If the
time of emergency operation is not sufficient, the battery needs to be fully recharged and the test is to be
carried out again. If the result of the test continues to be negative, the battery needs to be replaced.
CAUTION!
All damage that may occur as a result of the device being used contrary to this instruction will result in loss of
guarantee.
The guarantee shall not cover the light source and batteries.
Handling of obsolete equipment
Pursuant to the Act of 29 July 2005 on
waste
electrical
and
electronic
equipment and the Act of 24 April 2009
on batteries and accumulators, the
presented device, after use, due to
hazardous substances contained in it, is
subject to collection of waste electrical
and electronic equipment. Detailed
information on WEEE collection can be
obtained from municipal authorities.
Intelight Sp. z o.o.
8, Rydygiera str.
01 -793 Warsaw
Poland
KTM 97131 - Instruction Oximia, EN, ver.20161024
OXIMIA LED EMERGENCY LIGHTING FITTING
Installation and maintenance instructions
TECHNICAL SPECIFICATIONS:
Light source (non-replaceable):
White LED
Operating modes:
SA (M) - mains and emergency operation or
A (NM) - emergency operation
Emergency operation duration:
3 hours
Battery (non-replaceable):
Ni - Cd 800mAH / 3.6V
Battery charging duration:
24h
Power supply:
220 - 240V AC 50Hz
Max. power:
3W
Module:
Oximia LED
Visibility:
30 metres
Enclosure IP rating:
IP20
INTRODUCTION
1.
The lamp should be installed when power supply is off. Safety rules, construction and electrical installation
standards should be observed at all times.
2.
The lighting fitting should not be powered with circuits connected to inductive power-receiving devices at
the same time. This type of solution may cause damage to the electronic module of the lighting fitting.
3.
The lighting fitting should be used indoors.