background image

RECOMMENDED PERIODICAL MAINTENANCE

 

The lighting fitting should be tested on regular basis in accordance with valid laws and regulations. The results of 
the tests should be recorded and stored for the use of a fire safety inspector. 

One time daily

 

It has to be visually checked if the LED indicator in the lighting fitting lights up green. 

One time each month

 

It  is  necessary  to  disconnect  the  AC  power  supply  for  30  seconds  and  check  whether  the  lamp  is  operating  in 
emergency mode - the green LED indicator turns off, and 12 white LEDs light up.  

One time each year

 

Disconnect the AC power supply and test if the lamp operates in emergency mode  for a specified time. If the 
time  of  emergency  operation  is  not  sufficient,  the  battery  needs  to  be  fully  recharged  and  the  test  is  to  be 
carried out again. If the result of the test continues to be negative, the battery needs to be replaced. 

CAUTION!

 

All damage that may occur as a result of  the device being used contrary to this instruction will result in loss of 
guarantee.

 

 

The guarantee shall not cover the light source and batteries. 

 

Handling of obsolete equipment

 

 

Pursuant  to  the  Act  of  29  July  2005  on 
waste 

electrical 

and 

electronic 

equipment and the Act of 24 April 2009 
on  batteries  and  accumulators,  the 
presented  device,  after  use,  due  to 
hazardous substances contained in it, is 
subject  to  collection  of  waste  electrical 
and  electronic  equipment.  Detailed 
information  on  WEEE  collection  can  be 
obtained from municipal authorities.

 

 

 

Intelight Sp. z o.o.

 

8, Rydygiera str.

 

01 -793 Warsaw 

Poland

 

 

KTM 97131 - Instruction Oximia, EN, ver.20161024

 

 

OXIMIA LED EMERGENCY LIGHTING FITTING 

Installation and maintenance instructions 

 
 

 

 

TECHNICAL SPECIFICATIONS:

 

Light source (non-replaceable): 

White LED 

Operating modes: 

SA (M) - mains and emergency operation or 
A (NM) - emergency operation  

Emergency operation duration:  

3 hours  

Battery (non-replaceable): 

Ni - Cd 800mAH / 3.6V 

Battery charging duration: 

24h 

Power supply: 

220 - 240V AC 50Hz 

Max. power: 

3W 

Module: 

Oximia LED 

Visibility: 

30 metres 

Enclosure IP rating: 

IP20 

 
 
 

INTRODUCTION

 

1.

 

The lamp should be installed when power supply is off. Safety rules, construction and electrical installation 
standards should be observed at all times. 

2.

 

The lighting fitting should not be powered with circuits connected to  inductive power-receiving devices at 
the same time. This type of solution may cause damage to the electronic module of the lighting fitting. 

3.

 

The lighting fitting should be used indoors. 