Intel
®
Server System R1000WF Product Family System Integration and Service Guide
44
3.1
Power Supply Module – Installation / Removal
3.1.1
2
nd
Power Supply Module Installation
Figure 63. Power Supply Module Installation
1.
If installed, remove the insert from the chassis power supply bay.
2.
Insert the power supply module into the power supply bay (see Letter “B”).
3.
Push the power supply module into the bay until it locks into place.
3.1.2
Power Supply Module Removal
CAUTION
: The power supply is only hot-swappable (system does not have to be powered off) if the system
is configured with two power supply modules operating in a 1+1 redundant configuration only.
Systems with a single power supply installed or a system operating in a 2+0 non-redundant power mode,
must be powered off before removing the power supply module from the system.
1.
Detach the power cord from the power supply to be removed.
2.
While pushing the green latch in the direction shown, use the handle to pull the power supply module
from the system
Figure 64. Power Supply Module Removal