P140E 24 Hour Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be assigned as 24 Hour Zones. Only zones programmed at
this address will be active at all times. If a 24 hour zone has an entry delay assigned to it, the entry delay acts as
an abort timer e.g. the zone must be in alarm longer than the entry delay time before the alarm is activated. If the
zone is sealed before the entry delay expires, no alarm is generated.
P141E Non-Latching 24 Hour Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be assigned as Non-Latching 24 Hour Zones. A Non-
Latching 24 Hour Zone will operate as a normal 24 Hour zone except that when the zone re-seals the zone LED
and any assigned outputs will reset automatically.
P142E Lockout Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be assigned as Lockout Zones. A Lockout Zone will only
cause the alarm output to sound once during and armed period. If the lockout function is not programmed then the
zone can cause the audible alarms to sound on every zone alarm. In the case of a 24 hour zone, if this option is
turned on then the zone will only activate the alarm output/s once and must be reset by a code before another
alarm signal can operate the output/s again.
P143E Day Zone when Disarmed
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be assigned as Day Zones. A Day Zone can be used as a
door minder in a shop to warn when a customer has entered the premises. A day zone has the day zone function
when the alarm is disarmed, but becomes a normal security zone when armed. Day zones can be temporarily
disabled with the
“
Control
”
button if programmed to do so.
P144E Permanent Day Zone
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be assigned as Permanent Day Zones. A Permanent Day
Zone can be used as a door minder in a shop to warn when a customer has entered the premises. A Permanent
day zone will never cause an activation when the alarm is armed). Day zones can be temporarily disabled with the
“
Control
”
button if programmed to do so.
P145E Can Arm if not Sealed
Zones 1-8. (Default = No zones)
This option allows programming of which zones can be unsealed and still allow the panel to arm. Option 4 at
P170E must be on before this address has any effect. This option allows setting of the panel if low security areas
are not sealed at the time of arming.
P146E Report Excludes to Dialer
Zones 1-8. (Default = All zones)
If this option is on then the zone will report any exclusion (Bypass) of the zone to a Monitoring Station via Contact
ID or 4 + 2.
P147E Send Multiple Alarms to Dialer
Zones 1-8. (Default = All zones)
If this option is assigned to the zone, the zone can send multiple activation reports to a monitoring company
during any armed cycle. If off, the zone can only send one activation per armed cycle. In the case of a 24 hour
zone, if this option is turned off then the zone will only send one signal via the dialer and must be reset by a code
before another signal can be sent.
P148E Report Zone Tampers to Dialer
Zones 1-8. (Default = All zones)
This option allows the programming of zone tampers to be sent via the dialer to a Monitoring Station.
P149E Zone Reports Area
“
B
”
Account
Zones 1-8. (Default = All zones)
When a zone is in both partitions A&B this address allows the option of specifying which account number a zone
alarm will report to. The default is that a common zone will report to area A account code (P332E) but if this option
is on for a common zone it will report to area B account code (P333E).
P150E Inactivity Timer Zones
Zones 1-8. (Default = None)
This option allows the programming of which zones will be monitored for inactivity. All zones programmed with
this feature ON will be monitored for activity for the period set below (P240E). The inactivity timer only works
during the disarmed state and is accumulative, which means that if a zone does not trip at least once during a
disarm period the inactivity timer is not reset for that zone and will continue with the balance of the time period left
when the panel is next disarmed. The timer for each zone is reset every time a zone unseals.
PROGRAMMING ZONE INACTIVITY TIMER
P240E Inactivity Timer
- 0-255 Hours.
Default =120 Hours