MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.6.3 Selection Gas Type
Assign gas type of the attached gas transmitter.
Symbol
Description
Setting
Status
Gas
type
3
Function
Unit
1
Measuring
range
1
SP01
Sensor point
CO
Gas type
CO
CO
Ex
NO
NO
2
NH
3
O
2
CO
2
SO
2
H
2
S
CL
2
ETC
VOC
R4XX
R5XX
R11
R123
R134
R22
TEM
RH
CO
2
TOX
TEM
Carbon monoxide
Combustible gases
Nitrogen oxide
Nitrogen dioxide
Ammonia
Oxygen
2
Carbon dioxide
4
Sulphur dioxide
Hydrogen sulphide
Chlorine
Ethylene oxides
Air quality
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Refrigerant gas
Temperature
Humidity
Carbon dioxide
3
Toxic gas
Temperature
ppm
% LEL
ppm
ppm
ppm
Vol%
ppm
ppm
ppm
ppm
ppm
%
ppm
ppm
ppm
ppm
ppm
ppm
°F
%RH
ppk
ppm
°C
0-300
0-100
0-50
0-25
0-300
0-25
0-2000
0-100
0-200
0-100
0-20
0-100
0-300 / 2000
0-300
0-300
0-300
0-300 / 2000
0-300
XXXX
0-100
0-50
0-XXX
0-100
Symbol
Description
Setting
Status
Function
ppm
Unit
ppm
ppm
%LEL
Vol%
°F
%RH
%
ppk
°C
AF
Direction of the
alarm release
0
0 = Alarm release at increasing concentration
1 = Alarm 1 at falling, Alarm 2- 5 at increasing conc.
2 = Alarm 1 + 2 at falling, Alarm 3-5 at increasing c.
5 = Alarm 1-5 at falling concentration
1
Recommendation without obligation
2
Oxygen measurements: Alarm at falling concentration
3
Carbon dioxide measurements with unit ppk (1 vol% = 10 ppk)
4
Carbon dioxide measurements with unit ppm (1 vol% = 10.000 ppm)