MGC2 – UserManual
PolyGard
®
is a registered trademark of MSR-Electronic GmbH
4.5 Menu Relay Parameter
Reading and changes of the parameter for each single alarm relay.
OFF-Delay Time
0 s
Delay time for relay OFF
See 4.5.6
ON-Delay Time
0 s
Delay time for relay ON
See 4.5.6
External Mode
DI: ON = 0: OFF = 0
Definition external operation
See 4.5.5
Time Recurr. DI
0 s
0
0
Definition horn function
See 4.5.4
Latching Mode
No
Activation of latching mode
See 4.5.3
Static / Flash
0 s
Relay function
See 4.5.2
Relay Mode
De-energized
Relay mode
See 4.5.1
Relay Parameter
(Main menu)
R 01
(Selection relay No. – only registered modules possible)
4.5.1 Relay Mode
Definition of the relay mode – in activation status it is only overridden by the flashing function:
Symbol
Description Setting Status
Function
R 01
Relay No.
Selection relay
De-energized
Relay Mode
De-energized
De-energized = Alarm OFF = Relay OFF Energized
= Alarm ON = Relay OFF
4.5.2 Relay Function Static / Flash
Definition of the relay function – acts directly on the relay output:
Symbol
Description Setting Status
Function
R 01
Relay No.
Selection relay
0
Function
0
0
= Relay function static
> 0 = Relay function flashing (= time interval in sec.)
Impulse / Break = 1:1