5.3.1 Main Circuit Cable
Power cable selection requirements
For the selection of power cables, follow national or regional regulations. Selection of
IEC cables is based on the following:
●
EN 60204‑1 and IEC 60364‑5‑52 standards
●
PVC cable with copper conductors
●
Working properly when the ambient temperature is equal to or lower than 40℃
and the cable surface temperature is equal to or lower than 70℃ (Note: Contact
the manufacturer if the ambient temperature exceeds 40°C.)
●
Symmetrical cable with copper mesh shield
If the recommended cables for peripheral equipment or options are not suitable for
the product, contact Inovance.
To comply with the EMC standards, use shielded cables. The shielded cables are
divided into three‑conductor cables and four‑conductor cables, as shown below. If
the conductivity of three‑conductor cable shield cannot meet requirements, add an
independent PE cable or use a four‑conductor cable with one conductor as the PE. To
suppress radio frequency interference effectively, use the coaxial copper braid as the
cable shield. Ensure that the braided density is greater than 90% to enhance the
shielding performance and conductivity.
Summary of Contents for MD520 Series
Page 1: ......
Page 16: ...Components 15 Figure 2 2 Components of T5 to T6 models...
Page 19: ...Components 18 Figure 2 5 Components of T10 to T12 models with AC output reactor...
Page 27: ...System Structure 26 Figure 3 9 Control circuit terminals...
Page 43: ...Options 42 Figure 5 2 Dimensions of MD500 AZJ A1T2 through hole mounting bracket and holes mm...
Page 44: ...Options 43 Figure 5 3 Dimensions of MD500 AZJ A1T3 through hole mounting bracket and holes mm...
Page 45: ...Options 44 Figure 5 4 Dimensions of MD500 AZJ A1T4 through hole mounting bracket and holes mm...
Page 46: ...Options 45 Figure 5 5 Dimensions of MD500 AZJ A1T5 through hole mounting bracket and holes mm...
Page 47: ...Options 46 Figure 5 6 Dimensions of MD500 AZJ A1T6 through hole mounting bracket and holes mm...
Page 49: ...Options 48 Figure 5 8 Dimensions of MD500 AZJ A1T8 through hole mounting bracket and holes mm...
Page 54: ...Options 53 The following figures shows the installed copper busbar...
Page 115: ...Options 114 Figure 5 48 Dimension drawing of ferrite clamp...
Page 120: ...Expansion Cards 119 Figure 6 1 Installation position of expansion cards...