background image

Installation

DANGER

 

Install the product indoors and ensure the operating environment complies with the requirements described in 

the user guide.

 

◆ Install the product in a place free from strong magnetic field, direct sunlight, high temperature, inflammable 

gas, vapor, and dust. Failure to comply will result in the risk of explosion.

 

◆ Operate the product only in environments without drastic temperature changes or high humidity. Failure to 

comply may result in damage to the product due to formation of condensated water inside the product.

 

◆ Ensure all the cable connectors are connected securely to the product. Loose connections may result in I/O 

signal errors.

CAUTION

 

Install the product in environments with temperatures within the recommended storage temperature range. 

Failure to comply may result in display faults of the LCD.

Wiring

DANGER

 

◆ Cut off all the power supplies before installation, wiring, and plug-in/plug-out of cable connectors. Failure to 

comply will cause electric shock or circuit damage.

 

Wire

 the DC power supply to the dedicated terminals as described in the user guide.

 

Avoid metal chippings or cable terminals from falling into the product during screw hole machining and wiring. 

This is to prevent faults, component damage, and fire accidents.

 

Perform meticulous inspections after wiring to ensure the operating voltage and terminal positions are correct. 

Failure to comply may result in the risk of fire or accident.

CAUTION

 

◆ To avoid electric shock, cut off the power supply before connecting the power supply of the product.

 

◆ The product is powered up by a 24 VDC power supply. Power supplies outside ±20% of 24 VDC will result in 

severe damage to the product. Therefore, check whether the DC power supply provided by the switched-mode 

power supply is stable at a regular interval.

Operation and Maintenance

CAUTION

 

◆ Touch the HMI panel with hands or professional tools (such as a stylus) only during use. Inovance assumes no 

responsibility for panel damage caused by excessive external force.

 

◆ The lithium battery may contain elements that are harmful to personal health and the environment. Dispose of 

the battery according to local laws and regulations.

Safety recommendations

 

In positions where the operator touches the mechanical parts directly, such as positions for loading and 

unloading machinery tools, or positions where the machine operates automatically, manually-operated devices 

or other backup measures used to start or stop system operations must be available on site. Such devices or 

backup measures must be set independent of the programmable controller.

 

In cases where the program needs to be modified during system operation, use an encryption lock or other 

protective measures to allow the program to be modified by authorized operators only.

Disposal

CAUTION

 

Dispose of the product as an industrial waste.

1 Product Information

  1.1 Designation Rules

*5  &

4DSFFO%JNFOTJPO

&盘8JUI&UIFSOFUQPSU

5盘4UBOEBSEDPO珝HVSBUJPO

"VYJMJBSZ'FBUVSFT

1SPEVDU/BNF

*OPWBODFUPVDI

TDSFFO *OP5PVDI

1SPEVDU4FSJFT

盘ǜ

盘ǜ

TFSJFT

盘ǜ

盘ǜ

  1.2 Basic Parameters

Model

Description

IT7150E

  Inovance IT7000 series 15″ touch screen

Item

  Specifications

Item

  Specifications

Display dimension 15″

CPU

Cortex A8 (1 GHz)

Resolution

1024x768

DRAM

256 MB DDR3

Brightness (cd/m

2

) 300

Flash

256 MB

Display color

24-bit true color

RTC

Backlight source

LED

Serial port

COM1 (RS422/RS485); COM2 (RS232); COM3 (RS485)

Backlight service life 50000 hrs

Ethernet port

One 10 M/100 M adaptive RJ45 Ethernet port with 

 

LED indicator

Cable length within 100 m, CAT5/CAT5E

Cut-out dimensions 352x279

Mini USB type-B port One USB type-B port

Enclosure color

Silver

USB type-A port

One USB type-A port

 

Note: The USB type-A port provides current within 

200 mA only.

Safety Precautions

1) Read through the safety instructions before installing, operating, and servicing the product. 

2) To ensure personal and equipment safety, observe the notes indicated on the product labels and all the safety 

instructions in the user guide. 

3) The "CAUTION", "WARNING", and "DANGER" signs are only supplements to the safety instructions. 

4) Operate the product only in environments compliant with design specifications. Failure to comply may result in 

faults. Damage caused by improper usage is not covered by warranty.

5) Inovance shall take no responsibility of any personal injuries or property damages caused by improper usage.

Safety Levels and Definitions

DANGER

I

ndicates that failure to comply with the notice will result in severe personal injuries or even death.

WARNING

Indicates that failure to comply with the notice may result in severe personal injuries or even death.

CAUTION

Indicates that failure to comply with the notice may result in minor or moderate personal injury or 

 

                         damage to the equipment.

Keep this user guide in a proper place for future reference. Deliver this user guide to the end user.

Design

DANGER

 

◆ The interlock circuit and other circuits such as emergency stop, regular protection, and forward/reverse rotation 

circuits must be set independent of

 the product. Devices used to prevent equipment damage, such as up/down 

limit switches and reciprocating motion limit switches

, must also be set independent of the product.

 

◆ A fault protection circuit must be set independent of the product to prevent unexpected mechanical movement 

caused by, for example, errors in the non-detectable I/O control area.

 

◆ A user program must be designed to ensure safety of the user system in case of faults, including the display, 

control, communication, and power supply faults.

 

◆ Measures must be taken to avoid malfunction caused by communication faults between the product and the 

host controller, preventing personal injuries and equipment damage.

 

Do not bring live parts into contact with the metal enclosure of the product.

CAUTION

 

◆ Do not create switches that may result in personal injury or equipment damage on the touch screen. Use 

independent switches for critical operations. Failure to comply may result in accidents caused by wrong outputs 

or faults.

 

◆ Do not create switches used to control equipment safety operations on the touch screen, such as the emergency 

stop switch. Use independent hardware switches for safety-related operations. Failure to comply may result in 

severe personal injury or equipment damage.

 

◆ Do not use the product to alarm critical warnings that may cause severe personal injury, equipment damage 

or system stop. Use independent hardware/mechanical interlocks to design mechanisms used to alarm critical 

warnings and devices used to control/trigger such mechanisms.

Model

Description

Enclosure material

Front housing: 

aluminum alloy; 

Rear cover:  

sheet metal

SD card interface

One Micro SD card interface

Micro SD card supported, push-push type SD card 

slot

Operating 

temperature

0℃ to 50℃

DI/DO

8 DIs/4 DOs (reserved for customized needs)

8-channel DI detection, 4-channel transistor output

Storage temperature -20℃ to +70℃

Input voltage

24 VDC±20%

Working humidity

10%–90% RH (no 

condensation)

Rated current

800 mA

Cooling mode

Natural ventilation IP rating of the panel

Front panel: IP65; Rear cover: IP20

NOTE

 

◆ The design service life of the built-in button battery is five years. The actual service life of the 

battery varies with the operating conditions (temperature and humidify).

2 Mechanical Design Reference

    2.1 Installation Environment

1) The HMI is designed to operate in a temperature range between 0℃ to 50℃ (32℉ to 122℉), exceeding of which 

may cause component damage, malfunction, or function degradation. For use in special environments, contact 

 

the supplier.

2) Do not install the HMI in environments suffering from strong mechanical vibration.

3) Install the HMI into a cabinet with a depth of over 105 mm and reserve a surrounding clearance of at least 25 mm.

4) Install the HMI away from cables and devices generating strong interference, such as AC power supply cables, 

 

PLC output modules, AC drives, and relays. Use shielded cables for I/Os and ground the shielded cable properly.

5) The front panel of the HMI complies with IP65 requirements. 

The cabinet in which the HMI is installed must also 

comply with IP65 requirements, which means liquid sprayed to the surface of the cabinet will not penetrate into  

the cabinet.

    2.2 Mounting Dimensions

        

 

.PVOUJOH

IPMF

4JEFWJFX

*OUFSGBDF

'SPOUWJFX

3FBSWJFX

Model

Display 

Dimension

Outline Dimensions

Width x Height x Depth (mm)

Through-hole Mounting 

Dimensions (W x H) (mm)

Recommended  

Cut-out Dimensions (mm)

W+2

H+2

IT7150E

15″

367.8 x 294.8 x 53

350x277

352

279

2.3 Mounting Mode

See the following steps for through-hole mounting:

4IFFUNFUBMQBOFM

ʎ

ʍ

4FDVSFUIFNPVOUJOH

TDSFXTJOUPUIFNPVOUJOH

IPMFTPOCPUITJEFTPGUIF

).*FODMPTVSF

5JHIUFOUIFTDSFXTJOUIF

EJSFDUJPOJOEJDBUFECZUIF

BSSPX

1)  Put the HMI into the pre-drilled mounting holes in 

the cabinet  panel.

2)  Snap the eight metal clips (delivered by default) 

from the back of the cabinet panel into the 

eight mounting holes on both sides of the HMI 

enclosure (step ① in the figure).

3)  Tighten the mounting screws one by one until the 

HMI is secured to the cabinet panel (step ② in the 

figure). The recommended tightening torque is

 

6.0±0.5 kgf/cm (a tightening torque within this 

range achieves the waterproof purpose and 

avoids deformation).

CAUTION

 

To comply with IP65 sealing specifications, ensure all the mounting screws delivered are used and the 

 

                          curvature of the mounting panel is no greater than 0.010° after installation.

DANGER

 

Do not apply excessive force when tightening the mounting screws. If you have any question, contact the 

 

                          supplier.

3 Electrical Design reference

    3.1 Terminal Descriptions

11

12

侧视图

1

2

3

4

5

6

7

8

   

'SPOUWJFX

 

No. Name

Function

No.

Name

Function

1

Power 

supply 

ports

24 VDC power input ports of HMI, which are 

+24V and GND

(The power supply terminal used to connect 

power supply ports is delivered by default.)

7 Ethernet 

port

Ethernet communication port 

(RJ45) used to access a PC or PLC 

with LAN port

Thank for purchasing the IT7000 series human machine interface (hereinafter referred to as HMI) developed 

and manufactured by Inovance. The IT7150E HMI, which is developed based on Linux system, adopts Android-

style display featuring high resolution and high-performance processor featuring quick data processing and high 

response speed, providing users with excellent interactive experience.
The IT7150E HMI supports: 1) customized styles, VNC remote desktop, vector icons, and script programming; 

 

2) connection to PC through USB or Ethernet; 3) monitoring on PLC and PLC program upload/download for easy 

commissioning; 4) Modbus protocol and efficient communication with PLC; and 5) update of the HMI firmware, 

interface program, and recipe data through U-disk. When it is used with an Inovance PLC, you can update the 

PLC program for easy download of programs in the manufacturing devices on site. To facilitate HMI program and 

system commissioning, online simulation and offline simulation are available in IT7150E HMIs. 
This user guide describes the specifications, features, and usage of IT7150E HMIs. Read through this user 

guide before use to ensure a good understanding of product features and a safe use. For details on use of user 

program development environment and user program design methods, see the help file in the software tool 

"InoTouchPad".

 The latest version of InoTouchPad is released on www.inovance.com.

Safety Instructions

1

IT7150E HMI

User Guide

19011415      A00

MD500系列
通用变频器综合手册

MD500

由于本公司持续的产品升级造成的内容变更,恕不另行通知

A00

资料编码 19010306

版权所有 深圳市汇川技术股份有限公司

Copyright   Shenzhen Inovance Technology Co., Ltd.

服务与技术支持APP

官方微信

深圳市汇川技术股份有限公司

 

Shenzhen Inovance Technology Co., Ltd. 
地址:深圳市宝安区宝城70区留仙二路鸿威工业区E栋 
总机:(0755)2979 9595
传真:(0755)2961 9897 
客服:400-777-1260 
http://www.inovance.com

苏州汇川技术有限公司

 

Suzhou Inovance Technology Co., Ltd.
地址:苏州市吴中区越溪友翔路16号 
总机:(0512)6637 6666 
传真:(0512)6285 6720 
客服:400-777-1260 
http://www.inovance.com

Min

Max

综合手册

二维码

销售服务联络地址

条形码位置

放置二维码后删除虚框

2

3

*19011415A00*

Side view

Reviews: