background image

MEASURE OF SUCCESS

USER INSTRUCTIONS

Compact, PC-programmable

2-wire Transmitter with  

integrated M12 connectors

for Pt100 Input

The user instruction must be read prior to adjustment and/or installation. 

All information subject to change without notice.

1000311506 - 2015-10

GENERAL INFORMATION

IPAQ CT20 is a compact, analog, non-isolated, 2-wire temperature 

transmitter for Pt100 3W input with a temperature linear 4-20 mA 

output signal. The transmitter has integrated M12 connectors for both 

input and output connections.

The transmitter is configured from a PC via a USB port, connected via 

the INOR USB Interface, by using the ConSoft configuration program.

 

All necessary hardware and software for configuration are included 

in  the  ICON  configuration  kit,  except  the  M12  adapter  cable  USB 

Interface that must be ordered separately.

Inor offers a wide range of sensors for connection to the compact 

transmitter.

CT20

MEASURE OF SUCCESS

This product should not be mixed with other kind of scrap, after usage.

It should be handled as an electronic/electric device.

www.inor.com, www.inor.se

DATA (shortform)

CONFIGURATION

Installation of software and driver

 

    

 

 

 

     

Before making a configuration of IPAQ CT20 you need to do following:

1.     Install ConSoft 3 or higher and drivers for the USB Interface.

2.     Connect the USB Interface to a free USB port of your PC and  

 

  wait for automatic installation of the USB Interface.

 

Please  refer  to  “Quick  Installation  Guide  for  ConSoft  3”  for 

 

installation instructions.

 

 

 

      

Configuration procedure:

1.   Connect the output M12 connector on IPAQ CT20 to the PC via

 

 

the M12 adapter cable and USB Interface, LED indicator “DEV”  

 

on the USB Interface becomes green. (The transmitter is 

 

 

powered from the USB interface during configuration so no  

 

external power supply is needed)

 

2.   In  ConSoft  3,  click  on  the  “Read”  button.  The  software  will 

 

 

recognize the connected transmitter, upload the transmitter’s  

 

configuration and open the configuration window.

 

3.   In the configuration window you can configure: 

 

a.  measuring range

 

b.  measurement unit

 

c.  upscale or downscale action at sensor break

 

d.  input sensor compensation for known sensor errors

 

e.  TAG-number (16 characters)

4.   The selected configuration is downloaded to the transmitter by  

 

clicking the “Write” button. When the data transfer is complete,  

 

the transmitter begins using the new parameters directly.

INOR Process AB

, PO Box 9125, SE-200 39 Malmö, Sweden, 

Phone: +46-40-31 25 60, Fax: +46-40-31 25 70, E-mail: [email protected]

INOR Transmitter OY

, Unikkotie 13, FI-01300 Vantaa, Finland, 

Phone:+358-10-421 7900, Fax: +358-10-421 7901, E-mail: [email protected]

INOR Transmitter GmbH

, Duissernplatz 15, 

47058 Duisburg, Germany, 

Phone: +49-(0)203 86055-300, Fax: +49-(0)203 86055-333, 

 

E-mail: [email protected]

KROHNE Temperature Division INOR

, 7 Dearborn Road,

Peabody, MA 01960, USA, 

Phone: +1-978-826 6900, Fax: +1-978-535 3882, E-mail: [email protected]

Input

3-wire Pt100 IEC 60751, 

α

=0.00385

Output

Analog, 4-20 mA, temperature linear

Response time (90%)

< 10 ms

Measuring range limits

-50...+800°C 

Zero limits

-50°C to +50°C

Minimum span

50°C or 20°C, If the zero point is set at 
-40 °C, -20 °C, 0 °C, +20 °C or +40°C the
minimum span is 20 °C, otherwise it is 50 °C.

Sensor break

Selectable, Upscale (≥21.0 mA) or
downscale (≤3.6 mA) action

Sensor short-circuit

Fixed, downscale (≤3.6 mA) action

Ambient temperature

-40 to +85 °C (storage and operation)

Humidity

0 to 100 %RH

General data

Galvanic isolation

No

Power supply

7.5 to 32 VDC, polarity protected

Basic accuracy

Max. of ±0.2 °C or ±0.2 % of span

Process connection input

M12x1, 4-pin, A-coded, Female

Process connection output

M12x1, 4-pin, A-coded, Male